Packaged rooftop air conditioners cooling and gas/electric (76 pages)
Summary of Contents for Trane YHC092E
Page 1
3 – 10 Tons – 60 Hz YSC036E - YSC060E YHC036E - YHC067E Model Numbers YSC072F - YSC120F YHC092E - YHC120E YHC048F - YHC060F YHC072F - YHC092F SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Page 2
Carbon (HCFCs). Not all refrigerants containing these Revision Summary compounds have the same potential impact to the RT-SVX21K-EN (18 July 2012) environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs • MERV 8 filter with filter removal tool such as HCFCs and HFCs.
Model Number Description Switch without Barometric Relief for 21. Available for 3, 4, 5, 6, 7½, 8½ ton Clogged Filter Switch , Fan Failure horizontal configuration. standard/high efficiency models Switch and Condensate Drain Pan Barometric Relief for horizontal only. Overflow Switch configured units must be ordered Clogged Filter Switch , Discharge...
General Information Unit Inspection Compressor Nameplate As soon as the unit arrives at the job site The nameplate for the compressors are located on the side of the compressor. • Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
FFS (Fan Failure Switch) If air flow through the unit is not is powered by 24 VAC. proven by the differential pressure switch connected to the RTCI - ReliaTel™ Trane Communication RTOM (factory set point 0.07 “w.c.) within 40 seconds Interface (Optional)
General Information Compressor Disable (CPR1/2) Power Exhaust Control (Optional) This input incorporates the low pressure control (LPC) of ReliaTel Control each refrigeration circuit and can be activated by opening The power exhaust fan is started whenever the position of a field supplied contact installed on the LTB. the economizer dampers meets or exceed the power If this circuit is open before the compressor is started, the exhaust setpoint when the indoor fan is on.
This electronic sensor features single setpoint capability and timed override with override cancellation. It is used ReliaTel™ Option with a Trane Integrated Comfort™ building management system. This input incorporates the Frostat™ control (FOS) mounted in the indoor coil circuit and can be activated by...
General Information closing a field supplied contact installed in parallel with Maintenance Instructions provided with the literature the FOS. package for this unit. If this circuit is open before the compressor is started, the In order for the supply air smoke detector or return air compressor will not be allowed to operate.
Unit Dimensions Figure 1, p. 12 illustrates the minimum operating and Providing less than the recommended clearances may service clearances for either a single or multiple unit result in condenser coil starvation, “short-circuiting” of installation. These clearances are the minimum distances exhaust and economizer airflows, or recirculation of hot necessary to assure adequate serviceability, cataloged condenser air.
Page 13
Unit Dimensions Figure 2. 3-5 ton standard efficiency, 3 ton high efficiency Notes: 1. All dimensions are in inches/millimeters. 2. ½ NPT Gas Connection Figure 3. 3-5 ton standard efficiency, 3 ton high efficiency - roof curb Note: All dimensions are in inches/millimeters. 44 MM 44 MM 1038...
Page 14
Unit Dimensions Figure 4. 3-5 ton standard efficiency, 3 ton high efficiency - unit clearance and roof opening Note: All dimensions are in inches/millimeters. CLEARANCE 36” (914 MM) Figure 5. 6, 7½ (single) ton standard efficiency, 4-5 ton high efficiency Note: All dimensions are in inches/millimeters.
Page 15
Unit Dimensions Figure 6. 6, 7½ (single) ton standard efficiency, 4-5 ton high efficiency - roof curb Note: All dimensions are in inches/millimeters. (356 MM) (2130 MM) Figure 7. 6, 7½ (single) ton standard efficiency, 4-5 ton high efficiency - unit clearance and roof opening Note: All dimensions are in inches/millimeters.
Page 16
Unit Dimensions Figure 8. 7½ ton (dual) - 10 ton standard efficiency, 6 - 7½ (MCHE) ton high efficiency Note: All dimensions are in inches/millimeters. (TC MODELS) 2” ELECTRICAL CONNECTION (SINGLE POINT POWER WHEN HEAT INSTALLED) 1/2 NPT GAS CONNECTION (80 mbh, 120 mbh) 3/4 NPT GAS CONNECTION (150 mbh, 200 mbh, 250 mbh)
Page 17
Unit Dimensions Figure 10. 7½ ton (dual) - 10 tons standard efficiency, 6 - 7½ (MCHE) ton high efficiency - unit clearance and roof opening Note: All dimensions are in inches/millimeters. Figure 11. 7½ (dehumidification) - 10 ton high efficiency Notes: 1.
Page 18
Unit Dimensions Figure 12. 7½ (dehumidification) - 10 ton high efficiency - roof curb Notes: 1. All dimensions are in inches/millimeters. 18 1/2” (470 MM) 6 5/8” 83 7/8” (168 MM) 1” (2130 MM) (25 MM) 34 3/8” 56 3/8” (873 MM) (1432 MM) 18 1/2”...
Installation Pre-Installation If an element has detached from its ceramic insulator, carefully put it back into place. Replace the heater elements if they present symptoms WARNING noted in item 2 or 3 above. Fiberglass Wool! Procedure Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne WARNING...
Page 20
YSC090F 7½ YSC092F 8½ YSC102F 1047 YSC120F 1156 1058 YHC037E YHC048E/YHC047E YHC048F YHC060E/YHC067E YHC060F YHC072F 7½ YHC092E 1552 1335 7½ YHC092F 1124 1026 204/ 8½ YHC102E 1579 1362 YHC120E 1589 1372 (a) Weights are approximate. (b) Corner weights are given for information only.
Installation (a),(b) Table 2. Factory installed options (fiops)/accessory net weights (lbs) (continued) Coil Guards Economizer Electric Heaters Hinged Doors Manual Outside Air Damper Motorized Outside Air Damper Novar Control Oversized Motor — — Powered Convenience Outlet Powered Exhaust Reheat Coil —...
Page 22
Installation Figure 17. 4-6 ton high efficiency units, 7½ Figure 19. 3-5 ton standard efficiency units & 3 ton high (Microchannel) high efficiency unit and 6-10 efficiency units - Down flow supply & return air ton standard efficiency units - horizontal openings w/ through the base utilities supply &...
Installation Roof Curb Figure 22. View for base to roof curb alignment YHC092-120E (except YHC092F) on 50" x Downflow 84" roof curb The roof curbs for these units consists of a “full perimeter” enclosure to support the unit just inside of the unit base rail.
Installation A Rigging illustration and Center-of-Gravity dimensional Figure 25. Fork pockets - 7½ (Dehumidification) - 10 ton data table is shown in Figure 15, p. 20. Refer to the typical high efficiency units unit operating weights table before proceeding. 3. Remove all drill screws fastening wood protection to metal base rail.
Some, but not all units require a YSC092E**(H,Z), YSC102F**(H,Z), different TCO1 limit switch, which is attached to the YSC120F**(M,Y), YSC120F**(H,Z), combustion blower motor if horizontal discharge YHC092E**(M,Y),YHC092F**(M,Y), configuration is used. YHC102E**(M,Y), YHC120E**(L,X), YHC120E**(H,Z). Note: The following units require a limit switch change out for horizontal discharge.
Installation Figure 29. Duct cover WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be RTV Sealant inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 1.
Figure 34. Horizontal view 1 the TCO1 shipped attached to the combustion blower for horizontal operation. 4. Replace heat section access panel. Figure 32. TCO1 location (YHC092E-120E) TCO1 limit is located above the burner on the YHC092E, YHC102E, YHC120E models...
Figure 34, 28. For YHC047E-067E, YHC048E/F-060E/F ,YSC072F- • Inspect all control panel components; tighten any 120F , YHC092E-120E and YHC072F-092F units secure loose connections. the tab on left side to the indoor coil block off with one • Connect properly sized and protected power supply...
Installation Condensate Drain Configuration 4. Disconnect the 5" pipe nipple and union from the “Through the Base Gas” kit assembly. An evaporator condensate drain connection is provided 5. Using pipe sealant, attach the 6½” nipple and gas on each unit. Refer to Figure 16, p.
Installation Field Installed Power Wiring A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 37, WARNING A condensate drain line must be connected to the P-Trap. Proper Field Wiring and Grounding Pitch the drain lines at least 1/2 inch for every 10 feet of Required!
Installation Figure 38. All units except 7½ (dehumidification)-10 ton WARNING high efficiency units Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Installation Control Power Transformer Table 5. Electromechanical thermostat 24V AC conductors with electromechanical unit The 24 volt control power transformers are to be used only with the accessories called out in this manual. Distance from Unit Recommended to Control Wire Size Transformers rated greater than 50 VA are equipped with internal circuit breakers.
Page 35
Installation Figure 45. Electromechanical control customer low voltage routing (all units except 7½ (dehumidification) - 10 ton high efficiency) Figure 46. ReliaTel control customer low voltage routing (all units except 7½ (dehumidification) - 10 ton high efficiency) RT-SVX21K-EN...
Page 36
Installation Figure 47. ReliaTel (without TBUE) control customer wire routing (7½ (dehumidification) - 10 ton high efficiency) Figure 48. ReliaTel (with TBUE) control customer wire routing (7½ (dehumidification) - 10 ton high efficiency) RT-SVX21K-EN...
Page 37
Installation Figure 49. Electromechanical (without TBUE) control customer wire routing (7½ (dehumidification) - 10 ton high efficiency) Figure 50. Electromechanical (with TBUE) control customer wire routing (7½ (dehumidification) - 10 ton high efficiency) RT-SVX21K-EN...
Installation Smoke Detector Customer Low Figure 52. Up to 10 HVAC units If you have more than 5 HVAC units, you can connect all Voltage Wiring the supplies together on one power supply (up to 10 HVAC units), and all the returns together (up to 10 HVAC When interlocking System Sensor smoke detectors units) on another power supply.
Page 41
Installation Table 7. Temperature vs. resistance Table 9. Iron pipe size (SI) millimeters Temperature Iron Pipe Size (SI) Millimeters Degrees F° Degrees C° Nominal Resistance Length of Pipe 15 mm 20 mm 25 mm 32 mm 40 mm -20° -28.9° 170.1 K - Ohms (Meters) Pipe...
Pre-Start Use the checklist provided below in conjunction with the within the proper tolerances, notify the power company to “General Unit Requirements” checklist to ensure that the correct this situation before operating the unit. unit is properly installed and ready for operation. Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail.
Pre-Start • Close the field supplied main power disconnect switch Close the main power disconnect switch and the unit or circuit protector switch that provides the supply mounted disconnect switch, if applicable. power to the unit. Note: Upon closing main power disconnect and the unit Note: Upon closing main power disconnect and the unit mounted disconnect switch or circuit breaker, the mounted disconnect switch or circuit breaker, the...
Pre-Start Table 10. Service test guide for component operation Test Multi-Speed Fan Step Mode Econ Comp 1 Comp 2 Heat 1 Heat 2 Resistance Output Output Minimum Position Setpoint 0% Ω 2.2K Minimum Selectable Ventilation Economizer Ω Open 3.3K Test Open Cool Minimum Ω...
Page 45
Pre-Start Cool 1 Connect red thermostat wire (R) to yellow thermostat wire (Y1). Cool 2 Connect red thermostat wire (R) to yellow thermostat wire (Y2). Heat 1 Connect red thermostat wire (R) to brown thermostat wire (W1). Heat 2 Connect red thermostat wire (R) to brown thermostat wire (W2).
Unit Start-Up Verifying Proper Air Flow 1. Measure the supply and return duct static pressure and sum the resulting absolute values, 2. Use the accessory pressure drop table in the Service WARNING Facts, to calculate the total static pressure drop for all of the accessories installed on the unit;...
Unit Start-Up direction of rotation is indicated by an arrow on the fan Using the Service Test Guide in Table 10, p. 60, housing. momentarily jump across the Test 1 & Test 2 terminals on LTB1. Repeat process until Service Test Mode is at Cool 2 With the fan operating properly, determine the total (2-Steps of Cooling Applications Only) or Cool 3 (3-Steps system airflow (CFM) by (ReliaTel/Electromechanical):...
Unit Start-Up 1. Measure the DC voltage across pins Vt and com on the provides a constant CFM base on voltage output for the MMC board or note the DC voltage shown on the ECM potentiometer on the RTOM board. Before starting the board display.
Unit Start-Up below. Failure to follow these instructions will prevent the smoke detector from performing its design function. WARNING Live Electrical Components! Economizer Start-Up During installation, testing, servicing and troubleshooting of this product, it may be necessary to WARNING work with live electrical components. Have a qualified licensed electrician or other individual who has been Live Electrical Components! properly trained in handling live electrical components...
Unit Start-Up 4. To stop the SERVICE TEST, turn the main power the supply temperature rises 10°F more than when in disconnect switch to the “Off” position or proceed to cooling mode stage 2. the next component start-up procedure. Remove Monitor the suction pressure for 15 minutes.
Maintenance Fan Belt Adjustment - Belt Drive Note: Actual belt deflection “force” must not exceed the maximum “force” value shown in Figure 56, p. Units 7. Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”...
Maintenance Return Air Smoke Detector Maintenance • Record this data on an “operator’s maintenance log” like the one shown in Table 14, p. 54. If the operating Airflow through the unit is affected by the amount of dirt pressures indicate a refrigerant shortage, measure the and debris accumulated on the indoor coil and filters.
Page 53
Maintenance Microchannel (MCHE) Coils 2. Protect all electrical devices such as motors and controllers from any over spray. 3. Straighten any bent coil fins with a fin comb. NOTICE: Coil Damage! WARNING DO NOT use any detergents with microchannel Hazardous Pressures! condenser coils.
Maintenance 11. Restore the unit to its operational status and check system operation. Annual Maintenance • Clean and repaint any corroded surface. Final Process For future reference, you may find it helpful to record the unit data requested in the blanks provided. Complete Model Number: Unit Serial Number: Wiring Diagram Numbers...
Troubleshooting ReliaTel™ Control modes. If a problem in operation is noted in any mode, you may leave the system in that mode for up to one hour while troubleshooting. Refer to the sequence of The RTRM has the ability to provide the service personnel operations for each mode, to assist in verifying proper with some unit diagnostics and system status information.
Troubleshooting System Failure the previous section for the recommended troubleshooting procedure. • Measure the voltage between terminals J6-9 & J6-6. Heating Failure • Normal Operation = approximately 32 VDC Verify Heat Failure by Ignition Module (IGN) LED indicator: • System Failure = less than 1 VDC, approximately 0.75 OFF: No Power or Failure •...
Troubleshooting After approximately 30 seconds, turn the “Mode” Sensor Module electrically removed from the selection switch to the desired mode, i.e. Heat, Cool or system. Auto. Test 1 - Zone Temperature Thermistor Method 2 (ZTEMP) To reset the system at the unit, cycle the unit power by This component is tested by measuring the resistance turning the disconnect switch “Off”...
Troubleshooting ReliaTel Refrigeration Module (RTRM) leads for the opposite direction. The LED should have at least 100 times more resistance in reverse direction, as Default Chart compared with the forward direction. If high resistance in If the RTCI loses input from the building management both directions, LED is open.
Troubleshooting Heating Failure 5 Flashes: OA Quality Sensor 6 Flashes: OA Humidity Sensor Verify Heat Failure by Ignition Module (IGN) LED indicator: 7 Flashes: OA Temp Sensor • OFF: No Power or Failure 8 Flashes: MA Temp Sensor • ON: Normal 9 Flashes: RAM Fault •...
Troubleshooting Test 1 The resistance should be approximately 390 Ohms. Replace the Switch if it is open. Verifying that the economizer actuator (ECA) is functional: Replace the ECA if it is out of range. 1. Using the “Test Mode” described in the “System Start- Up”...
Unit Wiring Diagrams Numbers Note: Wiring diagrams can be accessed using e-Library by entering the diagram number in the literature order number search field or by contacting technical support. Table 17. Unit wiring diagram numbers Schematic Type Drawing Number Description 4366-7217 YHC(037-067) 4366-4571...
If you wish further help or information This limited warranty is extended by Trane to the original concerning this limited warranty, contact: purchaser and to any succeeding owner of the real...