Toshiba RAV-SM564UT-E Service Manual page 94

Air-conditioner split type
Hide thumbs Also See for RAV-SM564UT-E:
Table of Contents

Advertisement

Toshiba SDI / DI tuotteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy.
Sensor lamp part
Remote
controller
Block indication
indication
Operation Timer
Ready
Flash
l
¥
¥
F01
ALT
Indoor unit Heat exchanger sensor (TCJ) error
l
¥
¥
F02
ALT
Indoor unit Heat exchanger sensor (TC) error
l
¥
¥
F10
ALT
Indoor unit Room temp. sensor (TA) error
l
¥
¥
F29
SIM
Indoor unit Other indoor P .C. board error
l
¥
¥
P01
ALT
Indoor unit Indoor fan error
l
¥
¥
P10
ALT
Indoor unit Overflow detection
l
¥
¥
P12
ALT
Indoor unit Indoor fan error
l
¥
¥
P31
ALT
Other indoor unit error
By unit with warning No.
ALT
Error in indoor group
LAN system communication error
¥
¡
¥
L20
SIM
LAN system communication error
There are multiple communication adapters.
ALT (Alternate): Alternate flashing when there are two flashing LED
Representative defective position
Detection
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Network adapter
Network adapter/
Center
Network adapter/
Center
Network adapter
www.ilmalämpöpumput.com
SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Explanation of error contents
Open/Short of heat exchanger (TCJ) was detected.
Open/Short of heat exchanger (TC) was detected.
Open/Short of room temp. (TA) was detected.
EEPROM error (Other error may be detected. If no error, automatic address is repeated.
Indoor AC fan error was detected. (Fan thermal relay worked.)
Float switch worked.
Indoor fan error (Over-current / Lock, etc.) was detected.
Other indoor under condition of warning in group. E03/L07/L03/L08 warning
Sub remote controller error in a group
(Details of remote controller are displayed with unit No. Only central control side is displayed.)
Communication error of central control system signal
∗ Is not displayed on the remote controller
Duplicated indoor address of central control system communication
There are multiple communication adapters on remote controller communication line.
<In case of SP110, SP140>
l
¡
¥
: Go on,
: Flash,
: Go off
Automatic
Operation
reset
continuation
¡
×
¡
×
¡
×
×
×
×
×
×
×
×
×
¡
×
¡
¡
¡
×
¡
¡