No.
Part name
1. Detachment
Heat
11
exchanger
1) Recover the refrigerant gas.
2) Carry out work of item 1 of
3) Remove refrigerant pipe at indoor unit side.
4) Remove the fixing screws and then
5) Remove the drain hose from the drain
6) While pushing the heat exchanger, remove
2. Attachment
1) Mount the heat exchanger with the fixing
2) Fix the parts as before in order of drain
3) Connect the refrigerant pipe as before and
4) Following to work of item 2 of
Procedure
remove the piping cover. (Ø4 ×10, 3 pcs.)
pump and remove the fixing screws to
remove the drain pump stand.
(Ø4 ×8, 3 pcs.)
the fixing band, fixing screws and the heat
exchanger. (Ø4 ×8, 3 pcs.)
band and the fixing screws. (Ø4 ×8, 3 pcs.)
pump stand → piping cover.
then apply vacuuming.
the parts as before.
Fixing band
Heat exchanger
www.ilmalämpöpumput.com
10
.
Fixing screws (Ø4 ×10)
Fixing screws (Ø4 ×10)
Drain pump stand
Drain pump stand
10
, attach
Fixing screws
(Ø4 ×10)
– 190 –
Remarks
Piping cover
Fixing screws
Fixing screws
(Ø4 ×10)
(Ø4 ×10)
Fixing screw
Fixing screw
Fixing band
Fixing band