Toshiba RAV-SM564UT-E Service Manual page 152

Air-conditioner split type
Hide thumbs Also See for RAV-SM564UT-E:
Table of Contents

Advertisement

Toshiba SDI / DI tuotteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy.
DN
Item
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
Louver type
19
(Adjustment of air direction)
In automatic cooling/heating, temp.
width of cool → heat, heat →
1E
cool mode selection control point
28
Automatic reset of power failure
2A
Selection of option / error input (CN70)
Selection of thermostat output
2b
ƒ
(T10
)
2E
Selection of HA (T10) terminal
AUTO grille
30
(This function is not provided.)
31
Fan (Single operation)
32
Sensor selection
Humidifier control
40
(+Drain pump control)
(This function is not provided.)
<4-way Discharge Cassette type>
High ceiling selection
(Air volume selection)
5d
<Slim Duct type>
External static pressure
60
Timer setting (Wired remote controller)
Function selection item No. (DN) list
Contents
0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
to
0099: Undecided
0000: No shift
0002: +2°C
to
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0000: (1-way air discharge cassette)
0001: (4-way air discharge cassette) to 0037
0000: Undecided
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit in group
0000: No louver model
(0002:1-way)
0004: 4-way
0000: 0 deg
to
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0000: Filter input
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0002: Fire alarm input
0000: Impossible
0000: Impossible
0000: Body TA sensor
0000: No control
0001: Humidifier + Vaporizing type (Pump ON)
0002: Humidifier + Supersonic type
(Pump ON when specified time elapsed)
0003: Humidifier + Natural drain type (Pump OFF)
0000: Standard filter
0001: Super long life
0003: High performance (65%), High performance (90%),
(0006:Deodorant, Ammonia deodorization)
0000: Standard (At shipment)
0001: High static pressure 1
0003: High static pressure 2
0006: High static pressure 3
0000: Operable
www.ilmalämpöpumput.com
– 152 –
0001: 150H
0003: 5000H
0005: Clogging sensor used
0064: No.64 unit
0001: +1°C
0010: +10°C
(Up to +6 is recommended.)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Master unit in group
0001: Swing only
(0003:2-way)
0010: 10 deg
0001: Provided
0001: Alarm input
(Air cleaner, etc.)
0001: Card input
(Forgotten to be off)
0001: Possible
0001: Possible
0001: Remote controller sensor
(10 Pa)
(20 Pa)
(35 Pa)
(50 Pa)
0001: Operation prohibited
At shipment from factory
According to type
0000: Standard
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
According to model type
0003: 3 deg
(Ts±1.5)
0000: None
0002: Humidifier
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Impossible
0000: Body sensor
0003: Humidifier ON
Pump OFF
0000: Standard
0000: Standard
0000: Operable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents