Toshiba RAV-SM564UT-E Service Manual page 123

Air-conditioner split type
Hide thumbs Also See for RAV-SM564UT-E:
Table of Contents

Advertisement

Toshiba SDI / DI tuotteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy.
Check Code List (Outdoor)
¡
: Go on,
Sensor lamp part
Remote
controller
Block indication
indication
Operation Timer
Ready
Flash
¥
¥
¡
F04
ALT
Outdoor unit Discharge temp. sensor (TD) error
¥
¥
¡
F06
ALT
Outdoor unit Temp. sensor (TE, TS, TL) error
¥
¥
¡
F08
ALT
Outdoor unit Outside temp. sensor (TO) error
¥
¥
¡
F12
ALT
Outdoor unit Temp. sensor (TS) error
l
l
¥
H01
Outdoor unit Compressor break down
l
l
¥
H02
Outdoor unit Compressor lock
l
l
¥
H03
Outdoor unit Current detection circuit error
l
¥
¥
P03
ALT
Outdoor unit Discharge temp. error
l
¥
¥
P05
ALT
Power supply error
l
¥
¥
P22
ALT
Outdoor unit Outdoor fan error
l
¥
¥
P26
ALT
Outdoor unit Inverter Idc operation
l
¥
¥
P29
ALT
Outdoor unit Position detection error
l
l
No remote controller master unit
¥
E01
Remote controller communication error
l
l
¥
E02
Remote controller send error
l
l
Regular communication error between indoor and
¥
E03
remote controller
l
l
¥
E04
Indoor/Outdoor serial error
l
l
¥
E08
Duplicated indoor addresses
l
l
¥
E09
Duplicated main remote controllers
l
l
¥
E10
Communication error between CPU
l
l
Regular communication error between master and
¥
E18
follower indoor units
l
¥
¥
L03
SIM
Duplicated indoor master units
l
¥
¥
L07
SIM
There is group cable in individual indoor unit.
l
¥
¥
L08
SIM
Unset indoor group address
l
¥
¥
L09
SIM
Unset indoor capacity
¥
¡
¥
L30
SIM
Outside error input to indoor unit (Interlock)
l
¥
¥
P19
ALT
4-way valve inverse error
l
¥
¥
F01
ALT
Indoor unit Heat exchanger sensor (TCJ) error
l
¥
¥
F02
ALT
Indoor unit Heat exchanger sensor (TC) error
l
¥
¥
F10
ALT
Indoor unit Room temp. sensor (TA) error
l
¥
¥
F29
SIM
Indoor unit Other indoor P .C. board error
l
¥
¥
P01
ALT
Indoor unit Indoor fan error
l
¥
¥
P10
ALT
Indoor unit Overflow detection
l
¥
¥
P12
ALT
Indoor unit Indoor fan error
l
¥
¥
P31
ALT
Other indoor unit error
By unit with warning No.
ALT
Error in indoor group
LAN system communication error
¥
¡
¥
L20
SIM
LAN system communication error
There are multiple communication adapters.
l
¥
: Flash,
: Go off
ALT (Alternate): Alternate flashing when there are two flashing LED
Representative defective position
Remote controller
Remote controller
²
Remote controller
²
²
²
Network adapter
Network adapter/
Network adapter/
Network adapter
²
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
www.ilmalämpöpumput.com
Detection
Explanation of error contents
Outdoor
Open/Short of discharge temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Outdoor
Miswiring between TE sensor and TS sensor
Outdoor
Open/Short of outside temp. sensor was detected.
Outdoor
Open/Short of suction temp. sensor was detected.
When reached min-Hz by current release control, short-circuited current (Idc) after
Outdoor
DC excitation was detected.
Outdoor
Compressor lock was detected.
Outdoor
Current detection circuit error
Outdoor
Error was detected by discharge temp. release control.
Outdoor
Power supply voltage error
Outdoor
Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.
Outdoor
Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked.
Outdoor
Position detection error of compressor motor was detected.
Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
Indoor
No communication from remote controller and network adapter
Indoor
Serial communication error between indoor and outdoor
Indoor
Same address as yours was detected.
In 2-remote controller control, both were set as master.
(Indoor master unit stops warning and follower unit continues operation.)
Indoor
MCU communication error between main motor and micro computer
Regular communication was impossible between master and follower indoor units.
Indoor
Communication between twin master (Main unit) and follower (sub unit) was impossible.
Indoor
There are multiple master units in a group.
Indoor
When even one group connection indoor unit exists in individual indoor unit
Indoor
Indoor address group was unset.
Indoor
Capacity of indoor unit was unset.
Indoor
Abnormal stop by CN80 outside error input
Indoor
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up
Outdoor
ofTE, TS.
Indoor
Open/Short of heat exchanger (TCJ) was detected.
Indoor
Open/Short of heat exchanger (TC) was detected.
Indoor
Open/Short of room temp. (TA) was detected.
Indoor
EEPROM error (Other error may be detected. If no error, automatic address is repeated.
Indoor
Indoor AC fan error was detected. (Fan thermal relay worked.)
Indoor
Float switch worked.
Indoor
Indoor fan error (Over-current / Lock, etc.) was detected.
Indoor
Other indoor under condition of warning in group. E03/L07/L03/L08 warning
Sub remote controller error in a group
(Details of remote controller are displayed with unit No. Only central control side is displayed.)
Communication error of central control system signal
∗ Is not displayed on the remote controller
Center
Duplicated indoor address of central control system communication
Center
There are multiple communication adapters on remote controller communication line.
<In case of SP40, SP45>
SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Automatic
Operation
reset