Line/Load Connection; Drive-Cliq Interface X500 - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

3.3.3.3

Line/load connection

Table 3- 8
Connections for the Active Interface Module
Terminals
X1: L1, L2, L3
X2: U2, V2, W2
K4: 2/T1, 4/T2, 6/T3
(for frame sizes HI)
PE connection
Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1)
3.3.3.4

DRIVE-CLiQ interface X500

Table 3- 9
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Designations
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frequency: 47 ... 63 Hz
Connecting thread:
Frame size GI: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame size HI: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Connection for pre-charging circuit directly on pre-charging contactor:
Frame size HI: 2 x 16 mm² max. (3RT1034)
Connecting thread:
Frame size GI: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame size HI: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
DRIVE-CLiQ interface X500
PIN
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Line-side power components
3.3 Active Interface Modules, air-cooled
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
1)
1)
1)
1)
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120