Bosch FCS-320-TM Operation Manual page 16

Fcs-320-tm aspirating smoke detector
Hide thumbs Also See for FCS-320-TM:
Table of Contents

Advertisement

16
en | Technical Specifications
Figure 2.9 Example of the signal process of the airflow sensor in
case of malfunctions
Calibrating the Airflow Sensor
The airflow sensor calibration of the FCS-320-TM Aspirating Smoke Detector is performed
automatically when the detection unit is inserted into the housing base, provided that the X4
jumper has been plugged into another socket first. This plug-and-play feature makes the FCS-
320-TM considerably easier to commission. In addition, the calibration can also be performed
using the FAS-ASD-DIAG Diagnostic Software. The initialization phase is therefore carried out
according to or independently of the air pressure as desired.
Pipe System
A pipe system with an overall length of up to 50 m can be connected to FCS-320-TM series
Aspirating Smoke Detectors over a maximum of 8 aspiration points. A maximum of 5
aspiration points can be connected with ROOM·IDENT.
F.01U.130.928 | 1.0 | 2009.11
S
1
2
7
8
3
Operation Guide
FCS-320-TM Aspirating Smoke Detector
S Airflow sensor signal
t
Time
4
1
Normal airflow
2
Airflow too weak
6
3
Airflow too strong
4
Breakage
5
5
obstruction
6
Monitoring window
t
7
Delay
8
Malfunction message