6.23 Parameters for options
These parameters can be used only when specific optional parts are installed. Do not use these parameters
unless such parts are installed.
6.24 Permanent magnetic motors
6
• Function
Note 1: When using an PM motor, consult your Toshiba dealer, since the inverter is not compatible with all
Note 2: The inverter may fail to detect step-out in some cases, because it uses an electrical method to detect
: Parameter for option 1
: Parameter for option 2
: Parameter for option 3
: Parameter for option 4
: Parameter for option 5
: Step-out detection current level (for PM motors)
: Step-out detection time (for PM motors)
If the permanent magnet motor (PM motor) steps out and if the exciting current increases (it increases
in such a case) and remains above the value set with
the inverter will judge the motor to be stepping out and trip it. At that time, the trip message
"
" is displayed.
Title
Function
Step-out detection current level (for PM
motors)
Step-out detection time (for PM motors)
types of PM motors.
step-out. To avoid detection failures, you are recommended to install a mechanical step-out detector.
for the period of time set with
Adjustment range
10 ~ 150(%)
0.0 ~ 25.0 [sec]
F-86
E6581158
,
Default setting
100
1.0