• Communication parameters

Communication
Title
Function
No.
0800
Communication
band speed
0801
Parity
0802
Inverter number
0803
Communication
error trip time
0805
Communication
waiting time
0806
Setting of master
and slave
inverters for
communication
between inverters
(setting of master
and slave)
0811
Point 1 setting
0812
Point 1 frequency
0813
Point 2 setting
0814
Point 2 frequency
0829
Selection of
communication
protocol
0870
Block write data 1
0871
Block write data 2
0875
Block read data 1
0876
Block read data 2
0877
Block read data 3
0878
Block read data 4
0879
Block read data 5
0880
Free notes
0890
Parameter for op-
tion 1
0891
Parameter for op-
tion 2
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
-
-
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
-
-
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
-
1/1
0-255
s
1/1
0: (disabled)
1-100
s
0.01/0.01
0.00-2.00
-
-
0: Slave inverter (0 Hz command is-
sued in case the master inverter
fails)
1: Slave inverter (Operation contin-
ued in case the master inverter
fails)
2: Slave inverter (Emergency stop
tripping in case the master inverter
fails)
3: Master inverter (transmission of
frequency commands)
4: Master inverter (transmission of
output frequency signals)
%
1/1
0-100
Hz
0.1/0.01
0.0-500.0
%
1/1
0-100
Hz
0.1/0.01
0.0-500.0
-
-
0: Toshiba inverter protocol
1: Modbus RTU protocol
-
-
0: No selection
1: Command information 1
-
-
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
-
-
0: No selection
1: Status information
-
-
2: Output frequency
3: Output current
-
-
4: Output voltage
5: Alarm information
-
-
6: PID feedback value
7: Input terminal board monitor
-
-
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
-
1/1
0-65535
-
1/1
0-65535
-
1/1
0-65535
K-13
E6581158
Default
User
Reference
setting
setting
3
6.22
1
0
0
0.00
0
0
6.5.2
0.0
100
50.0 (WP)
60.0
(WN, AN)
0
6.22
0
0
0
0
0
0
0
0
0
6.23
0
11