6.20 Adjustment parameters

6.20.1 Pulse train output for meters

• Function
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
6
Note 1: The pulse length is fixed. Therefore, the duty is variable.
Note 2: The minimum pulse output rate is 38 PPS. Keep in mind that no pulses can be put out at any rate
: Logic output/pulse train output selection (OUT-NO)
: Pulse train output function selection (OUT-NO)
: Maximum nembers of pulse train
Pulse trains can be sent out through the OUT-NO output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.
=60.0,
=1,
Title
Function
Logic output/pulse train output
selection (OUT-NO)
Pulse train output function selection
(OUT-NO)
Maximum nembers of pulse train
smaller than 38 PPS.
=0,
=600
Adjustment range
0: Logic output
1: Pulse train output
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command
value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10:Inverter cumulative load factor
11: PBR (braking reactor) cumula-
tive load factor
12:Frequency setting value (after
PID)
13:VIA/II Input value
14:VIB Input value
15:Fixed output 1 (Output current:
100%)
16:Fixed output 2 (Output current:
50%)
17:Fixed output 3
(Other than the output current:
100%)
500-1600 (pps)
F-72
E6581158
Default setting
0
0
800