Component Test; Adjustments; Set Gas Input Rate - Carrier Series 100 Installation, Start-Up, And Operating Instructions Manual

Sizes 040-140, series 100 deluxe 4–way multipoise fixed-capacity condensing gas furnace
Hide thumbs Also See for Series 100:
Table of Contents

Advertisement

COMPONENT TEST

NOTE: The furnace control component test allows all compo-
nents to run for a short time; except the gas valve and humidifier
terminal HUM are not energized for safety reasons. The EAC-1
terminal is energized when the blower is energized. This feature
helps diagnose a system problem in case of a component failure.
The component test feature will not operate if any thermostat
signal is present ant the control and not until all time delays are
completed.
To Begin Component Self-Test:
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock,
personal injury, or death.
Blower access panel door switch opens 115-v power to
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the C
on control to the TEST/TWIN 3/16-inch quick-connect termi-
nal on control until the LED goes off. Remover jumper from
terminals. (See Fig. 36.)
NOTE: If TEST/TWIN and C
longer than 2 sec, LED will flash rapidly and ignore component
test request.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step g of
component test sequence.
c. After 7 seconds the hot surface igniter is energized for 15
sec., then off.
d. Blower motor operates on Continuous-FAN speed for 10
sec.
e. Blower motor operates on HEAT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec.
g. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from blower
door switch, and re-install blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting
below room temperature.
8. Verify that furnace restarts by raising thermostat setting above
room temperature.
Step 5—Adjustments

SET GAS INPUT RATE

Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft.
In the U.S.A., the input ratings for altitudes above 2000 ft must be
reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input ratings must be derated by 5 percent for
altitudes between 2001 ft to 4500 ft above sea level.
Furnace input rate must be within ± 2 percent of input on furnace
rating plate adjusted for altitude.
1. Determine natural gas orifice size and manifold pressure for
correct input.
-24v terminal
OM
-24v terminals are jumpered
OM
a. Obtain average gas heat value (at installed altitude) from
local gas supplier.
b. Obtain average gas specific gravity from local gas supplier.
c. Verify furnace model and size. Table 13 can only be used
for model 58MXB furnaces with rating plate heating inputs
(1000's Btuh) of 040 through 120. Table 14 can only be
used for model 58MXB furnaces with a heating size of 140.
d. Find installation altitude in Table 13 or 14.
NOTE: For Canadian altitudes of 2001 to 4500 ft, use U.S.A.
altitudes of 2001 to 3000 ft in Table 13 or 14.
e. Find closest natural gas heat value and specific gravity in
Table 13 or 14.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and manifold pressure
settings for proper operation.
EXAMPLE: (0-2000 ft altitude using Table 13)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45 and
Manifold pressure 3.6-in. wc
* Furnace is shipped with No. 45 orifices. In this
example all main burner orifices are the correct size
and do not need to be changed to obtain the proper
input rate.
Check and verify burner orifice size in furnace. NEVER ASSUME
ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
NOTE: Manifold pressure must always be measured with burner
enclosure front REMOVED. Gas meter must always be clocked
with burner enclosure front INSTALLED.
a. Remove burner enclosure front.
b. Remove seal cap that conceals adjustment screw for gas
valve regulator. (See Fig. 55.)
c. Jumper R and W thermostat connections on control to start
furnace.
d. Turn adjusting screw, counterclockwise (out) to decrease
manifold pressure or clockwise (in) to increase manifold
pressure.
NOTE: This furnace has been approved for a manifold pressure
of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft.
For altitudes above 2000 ft, the manifold pressure can be adjusted
from 2.0 in. wc to 3.8 in. wc. If manifold pressure is outside this
range, change burner orifices to obtain pressure in this range.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT bottom-out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in
excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
51