Carrier Series 100 Installation, Start-Up, And Operating Instructions Manual page 18

Sizes 040-140, series 100 deluxe 4–way multipoise fixed-capacity condensing gas furnace
Hide thumbs Also See for Series 100:
Table of Contents

Advertisement

DUCTS
TO
OUTDOORS
12" MAX
1 SQ IN.
VENT
PER 2000
B
THROUGH
BTUH*
ROOF
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
A
BTUH*
12" MAX
CIRCULATING AIR DUCTS
*Minimum dimensions of 3 in.
NOTE:
Use any of the following
combinations of openings:
A & B
C & D
D & E
→ Fig. 18—Air for Combustion, Ventilation, and
Dilution for Outdoors
If:
I
= combined input of all other than fan-assisted appli-
other
ances in Btu/hr
I
= combined input of all fan-assisted appliances in Btu/hr
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to
the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening shall
have free area of at least 1 in.
of the total input rating of all gas appliances in the space,
but not less than 100 in.
commence within 12" (300 mm) of the ceiling and the
second opening shall commence within 12" (300 mm) of
the floor. The minimum dimension of air openings shall be
at least 3 in. (80 mm). (See Fig. 19.)
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as
communicating spaces if connected by one or more perma-
nent openings in doors or floors having free area of at least
2
2 in.
/1,000 Btuh (4,400 mm
all gas appliances.
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having
1 SQ IN.
PER 4000
BTUH*
D
12"
MAX
F
1 SQ IN.
PER
4000
BTUH*
1 SQ IN.
PER
4000
BTUH*
E
G
12"
MAX
C
12" MAX
DUCT
1 SQ IN.
TO
PER 4000
OUTDOORS
BTUH*
F & G
2
2
/1,000 Btuh (2,000 mm
/kW)
2
2
(0.06 m
). One opening shall
2
/kW) of total input rating of
CIRCULATING AIR
DUCTS
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
Minimum of 3 in . . when type-B1 vent is used.
A03174
→ Fig. 19—Air for Combustion, Ventilation, and
free area of at least 1-in.
all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method,
infiltration should be adequate to provide air for combustion,
permanent ventilation and dilution of flue gases. However, in
buildings with unusually tight construction, additional air
MUST be provided using the methods described in the
Outdoor Combustion Air Method section.
Unusually tight construction is defined as
Construction with:
a. Walls and ceilings exposed to the outdoors have a continu-
ous, sealed vapor barrier. Openings are gasketed or sealed
and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical and gas lines, etc.
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used,
must not be smaller than 1/4-in. mesh. Louvers and grilles must be
constructed so they cannot be closed.
When combustion air ducts are used, they must be of the same
cross sectional area as the free area of the openings to which they
connect. The minimum dimension of ducts must not be less than 3
in. (80mm).
18
VENT THROUGH ROOF
Dilution from Indoors
2
/4,000 Btuh of total input rating for
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
UNCONFINED
SPACE
6" MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
A03175