Replacing The Batteries; Important Battery Safety Information; Battery Care And Storage Guidelines - HP R5500 User Manual

Hewlett-packard ups user guide
Hide thumbs Also See for R5500:
Table of Contents

Advertisement

To replace the component, reverse the removal procedure.
NOTE: Replacing the option card might require power management software to be restarted or
reconfigured.

Replacing the batteries

To replace the batteries:
Read and observe the requirements in "Important battery safety information (on page 34)" and
1.
"Battery care and storage guidelines (on page 34)."
Follow the instructions in "UPS battery replacement procedure (on page 35)."
2.

Important battery safety information

WARNING: The unit contains sealed lead-acid battery modules. To prevent fire or
chemical burns:
Do not attempt to recharge batteries after removal from the unit.
Do not disassemble, crush, or puncture the batteries.
Do not short the external contacts of the batteries.
Do not immerse the batteries in water.
Do not expose to temperatures higher than 60°C (140°F).
WARNING: To prevent personal injury from hazardous energy:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Do not place tools or metal parts on top of batteries.
WARNING: To prevent personal injury, prepare the area and observe all materials-
handling procedures when transporting a battery module. Battery modules weigh 20 kg
(44 lb).
NOTE: Replace all battery modules at the same time.

Battery care and storage guidelines

Minimize the amount of time the UPS uses battery power by matching the UPS configuration with the
utility voltage. Refer to "Configuring the UPS (on page 27)."
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside
of the UPS regularly with a vacuum cleaner.
Maintain the ambient temperature at 25°C (77°F).
If storing a UPS for an extended period, recharge the batteries every 6 months:
CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a backup. Do
not maintain an inventory of spare batteries on site unless a procedure to keep these batteries charged while
in storage is implemented.
Connect the UPS to utility power.
a.
Allow the UPS to remain in Standby mode.
b.
Allow the UPS to charge the batteries for at least 24 hours.
c.
Update the battery recharge date label.
d.
Maintenance 34