UPS model
R7000 INTL
1
The circuit breakers protect the C19 and C13 outlets.
2
If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension
bar is 10 A. The total maximum current for the extension bar is 12 A.

Power protection specifications

UPS model
R7000 NA/JPN
R7000 INTL

Voltage specifications

Configuration setting (VAC)
200/208
220
230
240

Output tolerance specifications

Source of power
Utility power (nominal
range)
Battery power

Output feature specifications

Feature
Online efficiency
Load
Circuit
segment
breaker
2
20 A¹
1
20 A¹
2
20 A¹
VA
Nominal power
rating (W)
7200
7200
6500
6500
Available nominal output voltage
(VAC)
204
220
230
240
Regulation
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
±5% of nominal output voltage rating
Specification
94% nominal input voltage
Output receptacles Maximum current
1 x L6-30R
Up to full UPS power rating
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
1 x IEC-309-32A
Up to full UPS power rating
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
Nominal voltage
setting
200/208, 220,
230, 240
220, 230, 240