UPS model
R5000 INTL
1
The circuit breakers protect the C19 and C13 outlets.
If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension
2
bar is 10 A. The total maximum current for the extension bar is 12 A.
Power protection specifications
UPS model
R5000 NA/JPN
R5000 INTL
Voltage specifications
Configuration setting (VAC)
200/208
220
230
240
Output tolerance specifications
Source of power
Utility power (nominal
range)
Battery power
Output feature specifications
Feature
Online efficiency
Voltage wave shape
Load
Circuit
segment
breaker
2
20 A¹
1
20 A¹
2
20 A¹
VA
Nominal power
rating (W)
5000
4500
5000
4500
Available nominal output voltage
(VAC)
204
220
230
240
Regulation
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
±5% of nominal output voltage rating
Specification
94% nominal input voltage
Sine wave; 5% THD with typical PFC load
Output receptacles Maximum current
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
1 x IEC-309-32A
Up to full UPS power rating
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
Nominal voltage
setting
200/208, 220,
230, 240
200/208, 220,
230, 240
Specifications 51