Ups Rear Panel; Repo Port - HP R5500 User Manual

Hewlett-packard ups user guide
Hide thumbs Also See for R5500:
Table of Contents

Advertisement

UPS rear panel

Item
1
2
3
4
5
6
7
8
9
10
11
12

REPO port

The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at
the UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port
must be connected to a remote, normally open switch (not supplied). The REPO switch is used in
conjunction with a main disconnect device that removes the AC source from the input of the UPS. When
the switch is closed:
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
Description
REPO port
Ground bonding screw
Communications port/option slot
Load segment 1 circuit breaker (controls the C19 and
C13 receptacles, but does not control the large output
receptacle)
Load segment 1 (two IEC-320-C19 receptacles, two IEC-
320-C13 receptacles, and one large output receptacle)
Load segment 2 circuit breaker
Load segment 2 (two IEC-320-C19 receptacles and two
IEC-320-C13 receptacles)
Battery circuit breaker
Cord retention clip attachment locations
ERM connector
Large output NEMA L6-30R receptacle (NA/JPN) or IEC-
309-32A receptacle (INTL) associated with load segment
1
Input power line cord with NEMA L6-30 plug (NA/JPN)
or IEC-309-32A plug (INTL)
Component identification 9