AC Receptacle Selection
The generator has two separate main power producing circuits. These two
circuits supply equal power to receptacles
shown when the voltage
selector switch is in the 120/240 V position.
When two or more receptacles are used; prevent overloading by dividing
the load between the two power circuits.
The chart below shows the rated load in amperes that can be connected
to each receptacle to balance the generator.
The total rated ampere draw is 25OA.
Main power circuit
Receptacles powered
Power distribution
by each main circuit
Main Circuit I
1,3,5and6
1+3+5+6=125Amax.
Main Circuit II
2,4 and 7
2+4+7=12.5Amax.
l
The table shows the specifications
when the 120/24OV Twist Lock
Receptacle is used for 12OV.
Example:
Receptacle 3 has a 1 OA load connected to it. Receptacle 5 has a 1 OA load
connected to it. Both receptacles are powered by main power circuit II. The
equation tells us that the total power draw on Circuit II is 20A. This is a
substantial overload of this circuit. To eliminate the excess power draw on
circuit II, the load from receptacle 5 should be switched to receptacle 2.
Now circuit I is powering the 10A load (less than 12.5A) and circuit II is
powering the 1 OA load (less than 12.5A).
@I 120V30A
@ 120V20A
@ 120V20A
@ 120V20A
@ 120V20A
@ 1201240 V 20A
@ 1201240 V 20A