● Control Outputs
● Alarm Outputs 1
and 2
•
Outputs are sent from terminals 1 and 2 with the E5CSV, and from
terminals 4 to 6 with the E5CS-U. The following diagrams show the
available outputs and their internal equalizing circuits.
v
+
+
①
①
L
②
②
GND
-
Relay
Voltage
E5CSV
•
The following table shows the specifications for each output type.
Output type
250 VAC, 3A (resistive load), electrical durability:
Relay
100,000 operations
PNP type, 12 VDC ±15%, 21 mA (with short-circuit
Voltage (PNP)
protection)
•
A voltage output (control output) is not electrically isolated from the
internal circuits. When using a grounding Sensor, do not connect any
of the control output terminals to the ground. (If control output
terminals are connected to the ground, errors will occur in the
measured temperature values as a result of leakage current.)
•
With the E5CSV-@1@@-@, alarm output 1 (ALM1) is output across
terminals 7 and 8.
•
On the E5CSV-@2@@-@, alarm output 1 (ALM1) is output across
terminals 7 and 8, and alarm output 2 (ALM2) is output across
terminals 6 and 8.
•
With the E5CS-@1@@U-@, alarm output 1 (ALM1) is output across
terminals 7 and 8.
•
On the E5CS-@2@@U-@, alarm output 1 (ALM1) is output across
terminals 7 and 8, and alarm output 2 (ALM2) is output across
terminals 7 and 9.
•
The following diagrams show the internal equalizing circuits for
alarm outputs 1 and 2.
⑥
ALM2
⑦
ALM1
⑧
E5CSV
•
The relay specifications are as follows:
SPST-NO, 250 VAC, 1 A (resistive load)
2.2 Wiring Terminals
v
+
+
④
④
L
⑤
⑤
GND
-
⑥
⑥
Voltage
Relay
E5CS-U
Specifications
⑦
ALM1
⑧
ALM2
⑨
E5CS-U
2-7