pROVISIONS FOR ADEqUATE COMBUSTION & VENTILATION AIR
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When
ventilating to an adjoining unconfined space, you must provide two
permanent openings: one within 12" of the ceiling and one within
12" of the floor on the wall connecting the two spaces (see options
1 and 2, Figure 5). You can also remove door into adjoining room
(see option 3, Figure 5). Each ventilation grill or opening shall have
a minimum free area of one square inch per 1,000 BTU/HR of the
total input rating of the gas equipment in the confined space.
Rework worksheet, adding the space of the adjoining
unconfined space. The combined spaces must have enough
fresh air to supply all appliances in both spaces.
The inlet connection is located on the right side of the gas valve.
Attach gas inlet line to gas valve.
If installing the an Optional Blower, it must be installed before
connecting the gas line.
Page 10
Figure 5
WARNING

CONNECTING THE GAS

Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one with 12" of the floor. Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces include attics and
crawl spaces. In most cases for direct communication with the
outdoors or direct communication through a vertical duct a free
area opening of one square inch per 4,000 BTU/HR of heater input
rating for each grill. If a horizontal duct is used, a grill free area or
duct opening shall have a free area opening of one square inch per
2,000 BTU/HR for each grill. Follow the National Fuel Code, ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation, or applicable
local codes, for required size of ventilation grills or ducts.
IMpORTANT: Do not provide openings for inlet or outlet air into attic
if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.