Provisions For Adequate Combustion & Ventilation Air - Empire Comfort Systems VFD26FM(2,3)0(N,W,C)(N,P)-2VFD26FM20NN-2 Installation Instructions And Owner's Manual

Vent-free gas fireplaces
Table of Contents

Advertisement

pROVISIONS FOR ADEqUATE COMBUSTION & VENTILATION AIR
This heater shall not be installed in a confined space or unusu-
ally tight construction unless provisions are provided for adequate
combustion and ventilation air.
A confined space is an area with volume less than 50 cubic feet per
1,000 Btuh of the combined input rates of all appliances drawing
combustion air from that space. Small areas such as equipment
rooms are confined spaces. Furnaces installed in a confined space
which supply heated air to areas outside the space must draw return
air from outside the space through tightly sealed return air ducts. A
confined space must have 2 openings into the space for combus-
tion air. One opening must be within 12 inches of the ceiling and
the other must be within 12 inches of the floor. The required sizing
of these openings is determined by whether inside or outside air is
used to support combustion, the method by which the air is brought
to the space (vertical or horizontal duct) and by the total input rate
of all appliances in the space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If your home meets all of the three criteria above, you must provide
additional fresh air. See "Ventilation Air From Outdoors," page
10.
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined
space.
Space: Includes the room in which you will install heater plus any
adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =
space)
Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling
height) = 1,280 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total volume
of the space.
2. Divide the space volume by 50 cubic feet to determine the
maximum BTU/Hr the space can support.
(volume of space) ÷ 50 cu. ft. = (maximum
BTU/Hr the space can support)
Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or
25,600 (maximum BTU/Hr the space can support)
30816-1-0912
3. Add the BTU/Hr of all fuel burning appliances in the space.
Example: Vented gas heater
*Do not include direct-vent gas appliances. Direct vent draws
combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum BTU/Hr the space can support with the
actual amount of BTU/Hr used.
Example:
25,600
38,000
If the area in which the heater may be operated is smaller than that
defined as an unconfined space or if the building is of unusually
tight construction, provide adequate combustion and ventilation
air by one of the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation,
or applicable local codes.
The space in the above example is a confined space because the
actual BTU/Hr used is more than the maximum BTU/HR the space
can support. You must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an adjoining room. If
the extra space provides an unconfined space, remove door
to adjoining room or add ventilation grills between rooms. See
Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See Ventilation Air From
Outdoors.
C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room
unconfined.
If the actual BTU/Hr used is less than the maximum BTU/Hr the
cu. ft. (volume of
space can support, the space is an unconfined space. You will need
no additional fresh air ventilation.
You must provide additional ventilation air in a confined
space.
Vent-free heater
Gas water heater
Gas furnace
Vented gas heater
G as fireplace logs
O ther gas appliances* +
Total
=
Vent-free heater
+
Total
=
BTU/Hr (maximum the space can support)
BTU/Hr (actual amount of BTU/Hr used)
BTU/Hr (maximum the space can support)
BTU/Hr (actual amount of BTU/Hr used)
WARNING
WARNING
BTU/Hr
BTU/Hr
BTU/Hr
BTU/Hr
BTU/Hr
BTU/Hr
BTU/Hr
20,000
BTU/Hr
18,000
BTU/Hr
38,000
BTU/Hr
Page 9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents