Gas Supply - Empire Comfort Systems White Mountain Hearth DVCX36FP91K-3 Installation Instructions And Owner's Manual

Direct-vent zero clearance gas fireplace heater
Table of Contents

Advertisement

The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Schedule 40 Pipe
Pipe
Inside Diameter
Length
Natural
0-10 feet
1/2"
10-40 feet
1/2"
40-100 feet
1/2"
100-150 feet
3/4"
NOTE: Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
NOTE: Since some municipalities have additional local codes, it
is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANSI Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANSI Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The Commonwealth of Massachusetts requires
that a flexible appliance connector cannot exceed three feet in length.
Gas Supply Pressure (inches w.c.)
Minimum
Natural Gas
4.5"
Propane Gas
11"
Manifold Pressure (inches w.c.)
Natural Gas
Propane Gas
Installing a New Main Gas Shut-Off (Check Local Code)
Each appliance should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of the
unit. Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
41366-0-0120

GAS SUPPLY

Tubing, Type L
Outside Diameter
Propane
Natural
Propane
3/8"
1/2"
1/2"
5/8"
1/2"
3/4"
1/2"
7/8"
Figure 9
Normal
Maximum
7.0"
14.0"
11.0"
14.0"
Normal (HI)
3.5"
10.0"
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
The appliance and its individual shut-off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system
3/8"
by closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
1/2"
or less than 1/2 psig (3.5 kPa).
1/2"
Attention! If one of the procedures results in pressures in excess
of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will
3/4"
result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural Gas valves have a built-in pressure
regulator in the gas valve. Natural Gas models will have a manifold
pressure of approximately 3.5 inch w.c. (.871 kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5 inch w.c.
(1.120 kPa) for the purpose of input adjustment to a maximum
of 14.0 inch w.c. (3.484 kPa). Propane Gas models will have a
manifold pressure approximately 10.0 inch w.c. (2.49 kPa) at the
valve outlet with the inlet pressure to the valve from a minimum of
10.8 inch w.c. (2.68 kPa) for the purpose of input adjustment to a
maximum of 14.0 inch w.c. (3.484 kPa).
2"
4 1/2"
Figure 10
Page 13

Advertisement

Table of Contents
loading

Table of Contents