E. Hearth Extension
WARNING
Fire Risk.
Hearth extension required to protect
combustible floors in front of appliance.
An 8 inch minimum hearth extension must be
constructed of non-combustible material.
NAILING TABS
(BOTH SIDES)
A
Cerona-36
Cerona-42
Figure 3.6
Hearth Extension Dimensions
10
B
A
B
in. 41-1/8
8
mm 1045 203
in. 48-1/8
8
mm 1222 203
Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. A • 6/06
8 in.
(203 mm)
1 in.
(25 mm)
WOOD OR OTHER
MARBLE, GRANITE, TILE OR
COMBUSTIBLE
OTHER NON-COMBUSTIBLE
FLOOR OR PLATFORM

HEARTH EXTENSION

Clearance to covered combustible hearth extension
Figure 3.7
6 in.
(152 mm)
COMBUSTIBLES UP TO
WOOD OR OTHER
1 INCH THICK ALLOWED
COMBUSTIBLE
UNDER THE OPENING
FLOOR OR
PLATFORM
Clearance to exposed combustible hearth extension
(6 inch Minimum to top surface of combustible
floor or floor covering.
Figure 3.8
BOTTOM OF
FIREPLACE
MAY BE
COMBUSTIBLE
MATERIAL
5-1/4 in.
(133 mm)
BOTTOM OF
FIREPLACE