Relay Outputs Worksheets - Honeywell ADEMCO VISTA-40 Programming Manual

2-partitioned security system
Hide thumbs Also See for ADEMCO VISTA-40:
Table of Contents

Advertisement

Relay Outputs Worksheets

Applicable only if relays (4204) or X-10 devices are used.
Programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the worksheet below and follow the
procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Notes: 1.
For 4204 the Device Programming section must be programmed for the device address. Set the DIP
switches on the device for that address.
2.
For X-10 devices, use the 1361X10 transformer in place of the transformer that comes in the box with the
control panel.
RELAY
S T A R T
A
DEV #
EV/ZL
1.
2.
3.
4.
5.
6.
7.
8.
A =
DEVICE ACTION
EV =
EVENT
ZL =
ZONE LIST
NOTES:
"START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device action starts.
"STOP" ZONE LIST:
ZT =
ZONE TYPE/SYSTEM OPERATION
Choices for Zone Types are:
00=zone not used
01=entry/exit 1
02=entry/exit 2
03=perimeter
04=interior (follower)
NOTE:
Choices for System Operation are:
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming (Code + Off)
*
Stop condition only
P =
PARTITION No. 1-2, 0 = Any
S T O P
ZT / P
ZL
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore
1-4, 0 = Not Used
Upon restore of ALL zones in this list, device action stops. It need not be same list as used for START.
05=day/night burglary
06=24-hour silent
07=24-hour audible
08=24-hour auxiliary
09=supervised fire
Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.
Any zone in "ZT" for Stop, that restores will stop the relay action.
23 = No Alarm Response
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
31 = End of Exit Time
41 = AC Power Fail
42 = System Battery Low
**
Or at disarming, whichever occurs earlier
1=4204
Restrict
2=X-10
ZT / P
10=interior (delay)
20=arm stay
21=arm away
22=disarm
23=no alarm response
– 33 –
Dev Add 4204
Relay # for 4204
or House Code
for X-10
Unit Code for X-10
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field 1*74) *
57 = YY Seconds (enter YY in field 1*75) *
58 = Duress
60 = Audio Alarm Verification (must be
selected for both START and STOP
operation)
or

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-128bpVista-250bpVista-128sia

Table of Contents