Download Print this page

Technical Specifications - Johnson Controls T600xxx-3 Series Product Bulletin

T600xxx-3 series

Advertisement

Technical Specifications

T600xxx-3 Series Thermostats
Power Requirements
Relay Contact Rating Maximum
Inductive
Digital Inputs
Economizer Output
Recommended Wire Size
Sensor Type
Temperature Range
Backlit
Display
Heating
Control
Cooling
Control
Accuracy
Temperature
Minimum Deadband
Ambient Conditions
Operating
Storage
Dimensions (H x W x D)
Compliance
United States
Canada
Europe
Australia and
New Zealand
Shipping Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada.
Controls Group
507 E. Michigan Street
Milwaukee, WI 53202
6
T600xxx-3 Series Thermostats Product Bulletin
Published in U.S.A.
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Voltage-Free Contacts across Terminal C to Terminals DI1 or DI2
0 to 10 VDC into 2k ohm resistance minimum (T600MEP-3 only)
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Local 10k ohm NTC thermistor
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
2F°/1C° between Heating and Cooling
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
CE Mark, EMC Directive 89/336/EEC
C-Tick Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
All other marks herein are the marks of their respective owners.
© 2006 Johnson Controls, Inc.
www.johnsoncontrols.com
.

Advertisement

loading

This manual is also suitable for:

T600hcn-3T600hpn-3T600msn-3T600hcp-3T600hpp-3T600mep-3 ... Show all