Power management
Consumption Limitation box
Figure 27: Consumption Limitation box
This setting has to be made if the Power Consumption Options → Consumption Mode was set to Limitation for the
system unit (first box on the page).
Limit Threshold
Specifies the limit threshold.
I
The value must be higher than the value currently reached. If you enter a value which is too low, the
system will automatically correct it to the next higher permissible value.
Warning Threshold (1 - 100)
Defines the warning threshold in percent of the Limit Threshold.
Enable Dynamic Power Control
Enables/disables the dynamic power control.
I
Default is disabled. If this option is enabled, the management blade controls the power consumption
of the system unit by reducing the performance of the server blades (using ACPI functions) as soon
as the Warning Threshold is reached.
Limit Duration Time (1 - 7200)
Defines the duration the limit status is accepted in seconds.
Action after Limit exceeded
Defines which action should to be taken with the system unit after reaching the defined limit.
Threshold Definition
You can set Relative or Absolute threshold. Depending on this setting the adjacent Limit Threshold field shows
(and requires) a percentage value (Relative) or a W or BTU/h value (Absolute).
Scheduled Consumption Configuration box
Figure 28: Scheduled Consumption Configuration box
This setting has to be made if the Power Consumption Options → Consumption Mode was set to Scheduled for the
system unit (first box on the page). Up to 2 different consumption modes per day can be set for each day of the
week (from Sunday to Saturday) or for Everyday.