Table 6. Battery
Configuration
(10) 12V, 5 Ah internal batteries
EBM Configuration
PW5125 120 EBM: 120V, 30A
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full load
discharge
External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to 90% usable capacity at nominal line voltage after full load discharge; an external charger
is recommended for faster recharge times when using more than 2 EBMs.
Monitoring
Advanced monitoring for earlier failure detection and warning; auto detection of additional EBMs
(if using LanSafe III Power Management Software, the EBM configurator must be used for
accurate reporting of EBM battery times).
Table 7. Battery Run Times (in Minutes at Full/Half Load)
Model
Internal UPS Batteries
2400 VA
7/19
3000 VA
5/15
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
Powerware
5125 Two-in-One (2400–3000 VA) User's Guide
®
1 EBM
2 EBMs
35/73
60/124
25/61
49/103
:
www.powerware.com
Specifications
3 EBMs
4 EBMs
85/177
110/229
69/146
90/190
49