Operation

(continued)
Resetting Your Inverter/Charger to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to "DC OFF" and remove some of the connected electrical load (ie: turn off some of the
AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to
either "AUTO/REMOTE" or "CHARGE ONLY."

Configuration

Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation
depending on your application.
B4
Group A DIP Switches
Using a small tool, configure your Inverter/Charger by setting the four Group A DIP Switches (located on the front panel of your unit; see
diagram) as follows:
Select Battery Type—REQUIRED
A1
CAUTION: The Battery Type DIP Switch setting must
match the type of batteries you connect, or your batteries
may be degraded or damaged over an extended period of
time. See "Battery Selection" for more information.
Battery Type
Gel Cell (Sealed) Battery
Wet Cell (Vented) Battery
Select Low AC Input Voltage
A4
A3
Point for Switching to Battery—
OPTIONAL*
Switch
Voltage
Position
105V
#A4 Up & #A3 Up
95V
#A4 Up & #A3 Down
85V
#A4 Down & #A3 Up
75V
#A4 Down & #A3 Down
(factory setting)
B3
B2
B1
Group B Dip Switches
A4
A3
A2
A1
Switch Position
Up
Down (factory setting)
A4
A3
A2
A1
* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger's Low AC Voltage Input Point
(DIP Switches #3 and #4 of Group A are set to 95V. However, if the unit frequently switches to battery power due to momentary low
line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. By decreasing the Low
AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.
A4
Charger Inhibit
A2
Function
Charger Inhibited
Charger Enabled
A4
A3
A2
A1
A4
5
A3
A2
A1
OUTPUT C/B 12A
Group A Dip Switches
A4
A3
A2
Switch Position
Up
Down (factory setting)
A3
A2
A1
A4
A3
A2
A1
A1