E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
Top Vent - Horizontal Termination
Venting with 1 elbow
V Minimum
SL-550TR-E
90 Elbow
2 ft.
610 mm
1/2 ft.
152 mm
2 ft.
610 mm
1-1/2 ft. 457 mm
3 ft.
914 mm
2-1/2 ft. 762 mm
5 ft.
1.5 m
3-1/2 ft.
1.1 m
7 ft.
2.1 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
Fire Risk.
When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented fi replaces, a one
foot minimum vertical vent section is required before
installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented fi replaces,
a three foot minimum vertical vent section is required before
installing fi rst elbow.
Figure 5.4
16
H
Maximum
1
SL-750TR-E
SL-950TR-E
2 ft.
610 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
3 ft.
914 mm
3 ft.
914 mm
5 ft.
1.5 m
5 ft.
7 ft.
2.1 m
7 ft.
14 ft.
4.3 m
14 ft.
WARNING
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. K • 9/08
WARNING
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
1.5 m
simple up and out installation
(see Figure 5.3).
2.1 m
4.3 m
H
1
V
1