Listing And Code Approvals; Appliance Certifi Cation; Gas Pressure Requirements; High Altitude Installations - Heat & Glo XLR-PLUS-N-AU Owner's Manual

Natural gas
Hide thumbs Also See for Heat & Glo XLR-PLUS-N-AU:
Table of Contents

Advertisement

1 1

Listing and Code Approvals

A. Appliance Certifi cation
MODELS: XLR-PLUS-N-AU, XLR-PLUS-PB-AU
LABORATORY: SAI Global
TYPE: Gas Space Heating Appliance
STANDARD: AS4553-2008
The Heat & Glo gas appliances discussed in this Installer's
Guide have been tested to certifi cation standards and listed
by the applicable laboratories.
This appliance must be installed in accordance with the
rules in force.
NOX Class 5 for G20, NOX Class 5 for G31
B. Gas Pressure Requirements
Pressure requirements for XLR-PLUS fi replaces are
shown in table below.
Two taps are provided on the right hand side of the gas
control for a test gauge connection to measure the inlet
and outlet pressures.
The fi replace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 3.4 kPa.
If the fi replace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
Inlet Pressure
Outlet Gas Pressure
Gas Rate
Maximum Gas Consumption
Burner Injector
Pilot Injector
Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum
inlet pressure of 3.4 kPa. For pressures over 3.4 kPa, an in line pressure regulator must be installed
upstream from the gas control valve.
8
Natural Gas
1.13 kPa
0.80 kPa
m3
.405
/
h
26 MJ/h
DMS 42 (2.350 mm)
Ø .023 (.584 mm)
Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. D • 6/11
C. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 610 meter elevation:
Reduce input rate 4% for each 305 meters feet above
610 meters.
D. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
E. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa-
per, plant fi bers, plastics, or other material that can ignite
and burn, whether fl ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
F. Electrical Codes
All electrical safety testing has been done following the EN
60335-2-102 standard. Local codes apply.
Propane
2.75 kPa
2.40 kPa
m3
.134
/
h
26.0 MJ/h
DMS .057 (1.450 mm)
Ø .014 (.356 mm)
Butane
2.75 kPa
2.40 kPa
m3
.111
/
h
22 MJ/h
DMS 55 (1.325)
Ø .010 (.254 mm)