Gas Information; Gas Pressure Requirements; Gas Connection - Heat & Glo XLR-PLUS-N-AU Owner's Manual

Natural gas
Hide thumbs Also See for Heat & Glo XLR-PLUS-N-AU:
Table of Contents

Advertisement

11 11

Gas Information

A. Gas Pressure Requirements
Pressure requirements for XLR-PLUS-AU fi replaces are
shown in Table 11.1 below.
Two taps are provided on the front face of the gas control
for a test gauge connection to measure the inlet and out-
let pressures. See Figure 11.1.
The fi replace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 3.4 kPa.
If the fi replace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 3.4 kPa.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 3.4 kPa.
PRESSURE
TAPS
VARIABLE
6V DC
VALVE
REGULATOR
Figure 11.1. Valve Components
Inlet Pressure
Outlet Gas Pressure
Gas Rate
Maximum Gas Consumption
Burner Injector
Pilot Injector
Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum
inlet pressure of 3.4 kPa. For pressures over 3.4 kPa, an in line pressure regulator must be installed
upstream from the gas control valve.
Table 11.1
ON/OFF REMOTE
TOGGLE SWITCH
8KI-CE
AUX300CE
MODULE
Natural Gas
1.13 kPa
0.80 kPa
m3
.405
/
h
26 MJ/h
DMS 42 (2.350 mm)
Ø .023 (.584 mm)
Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. D • 6/11
B. Gas Connection
Note: Have the gas supply line installed in accordance with
local building codes by a qualifi ed installer approved and/or
licensed as required by the locality.
Note: Before the fi rst fi ring of the appliance, the gas supply
line should be purged of any trapped air.
Note: Consult local building regulations to properly size the gas
supply line leading to the (Rp 1/2 in.) hook-up at the unit.
Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)
threaded gas inlet connection on the manual shutoff valve.
Leak test all gas line points and the gas control valve prior
to and after starting the gas appliance.
WARNING
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fi ttings and connections.
• Do not use open fl ame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available, non-
corrosive leak check solution. Be sure to rinse
off all leak check solution following testing.
Fittings and connections may have loosened
during shipping and handling.
Propane
2.75 kPa
2.40 kPa
m3
.134
/
h
26.0 MJ/h
DMS .057 (1.450 mm)
Ø .014 (.356 mm)
Butane
2.75 kPa
2.40 kPa
m3
.111
/
h
22 MJ/h
DMS 55 (1.325)
Ø .010 (.254 mm)