installing
Place the stove on a non-combustible floor
protector that extends a minimum of 6 inches
to the front, 2 inches to the sides and flush with
the rear of the hopper. Ash protection must also
be positioned under any horizontally run flue
pipe. The minimum floor protector material is 20
gauge sheet metal. Other floor protector materi-
als are ceramic tile, stone, brick, etc.
Place the stove away from combustible walls
at least as far as shown in Figures ,  and 4.
Note that the clearances shown are minimum
for safety but do not leave much room for access
when cleaning or servicing. Please take this into
account when placing the stove.
Connect the power cord to a 10 V.A.C. 60Hz
grounded receptacle. (A surge protector is recommended to
protect the circuit board.) If the voltage entering your home
is below 116 volts your stove may not work properly. Also be
sure that the polarity of the outlet that the stove is plugged
into is correct.
Prior to installing the flue pipe, connect a draft meter. (The
draft meter must have a minimum range of 0-.5.)Record the
first reading. Connect flue pipe to stove and be sure all doors
and windows in the home are closed. Record the second
draft reading_______. If the second reading is more than .05"
lower than the first reading, check for possible restrictions or
the need for outside air (see page 8). For more information
on the draft test procedure, refer to Page 0.
Mobile home installation
When installing this unit in a mobile home several re-
quirements must be followed (Reference HUD Regulation
#4CFR80):
1. The unit must be bolted to the floor. This can be done by
using clips (part # -0-677110) and 1/4" lag screws.
. The unit must also be connected to outside air. See
page 8.
. Floor protection and clearances must be followed as
shown.
4. Unit must be grounded to the metal frame of the mobile
home.
cautiOn: this appliance must be vented to the out-
side.
cautiOn
the Structural integritY OF the
MObile hOMe FlOOr, wall, and
ceiling/rOOF MuSt be Maintained.
warning
Mobile home regulations do not allow
installation in a room designated for

installation

sleeping.
3"
12"
Fig. 3
Floor Protection must be 2 inches to each side, 6
inches to the front, and 0 inches to the back of the
stove. Floor Protector minimum: 32" wide x 32"
deep.
Fig. 4
6" from
pipe to wall
Fig. 5: Optional Top Vent Pipe Clearances
6.25"
Fig. 2
" minimum
0"
2"
side of
stove to
combustible
surface
6" from
glass
18"
4" from
back of top
flue vent to
wall
XXV Pellet Stove
6.25"
from
5