Venting - Harman Stove Company XXV Installation & Operating Manual

Pellet stove
Hide thumbs Also See for XXV:
Table of Contents

Advertisement

requirements for terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding.
NOTE: Only the Harman Direct Vent Wall Pass-through
(part # 1-00-677077) or PL listed vent pipe wall pass-
throughs and fire stops should be used when venting
through combustible materials.
NOTE: Always take into consideration the effects of
the prevailing wind direction or other wind currents
that may cause flyash and/or smoke when placing the
termination vent.
in addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
1
B. The clearance to a window or door that may be
opened must be a minimum of 48" to the side, 48"
below the window/door, and 1" above the window/
door.
1
(with outside air installed, 18" to side or below
window/door)
C. A 1" clearance to a permanently closed win-
dow is recommended to prevent condensation on
the window.
D. The vertical clearance to a ventilated soffit lo-
cated above the terminal within a horizontal distance
of  feet (60 cm) from the center-line of the terminal
must be a minimum of 18".
E. The clearance to an unventilated soffit must be
a minimum of 1".
F. The clearance to an outside corner is 11" from
center of pipe.
G. The clearance to an inside corner is 1".
H. A vent must not be installed within  feet (90 cm)
above a gas meter/regulator assembly when measured
from the horizontal center-line of the regulator.
V
= Vent terminal
6
XXV Pellet Stove

Venting

I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
J. The clearance to a non-mechanical air supply
inlet to the building or the combustion air inlet to any
other appliance must be a minimum of 48".
K. The clearance to a mechanical air supply inlet
must be a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be
a minimum of 7 feet.
M. The clearance under a veranda, porch, deck
or balcony must be a minimum of 1 inches.
NOTE: The clearance to vegetation and other exte-
rior combustibles such as mulch is 6" as measured
from the center of the outlet or cap. This 6" radius
continues to grade or a minimum of 7 feet below
the outlet.
Certain Canadian and or Local codes or regula-
1
tions may require different clearances.
A vent shall not terminate directly above a side-
2
walk or paved driveway which is located between
two single family dwellings and serves both dwell-
ings.
Only permitted if veranda, porch, deck, or bal-
3
cony is fully open on a minimum of  sides beneath
the floor.
nOte: where passage through a wall, or
partition of combustible construction is desired,
the installation shall conform to can/cSa-b365.
(if in canada)
1
1
1
1
1,2
1,3