Input Specifications - Omron CJ Series Operation Manual

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Specifications
2-1-3

Input Specifications

Thermocouple Input
Setting Ranges
No. Thermocouple type
K: −200 to 1,300°C
0
(−300 to 2,300°F)
1
K: 0.0 to 500°C
(0.0 to 900.0°F)
J: −100 to 850°C
2
(−100 to 1,500°F)
3
J: 0.0 to 400°C
(0.0 to 750.0°F)
T: −200.0 to 400.0°C
4
(−300.0 to 700.0°F)
L: −100 to 850°C
5
(−100 to 1,500°F)
L: 0.0 to 40 °C
6
(0.0 to 750.0°F)
7
R: 0 to 1,700°C
(0 to 3,000 °F)
8
S: 0 to 1,700°C
(0 to 3,000 °F)
9
B: 100 to 1,800°C
(300 to 3,200 °F)
See note 2.
Platinum Resistance
Thermometer Input
Setting Ranges
No. Thermocouple type
0
Pt100:
−200.0 to 650.0°C
(−300.0 to 1,200.0 °F)
1
JPt100:
−200.0 to 650.0°C
(−300.0 to 1,200.0 °F)
2 to
---
9
Note
16
A switch on the front of the Unit (pin 3 of the DIP switch) selects whether the
Temperature Control Unit's data is stored and indicated as 4-digit BCD or
binary (i.e., 4-digit hexadecimal). Pin 2 of the DIP switch selects whether the
temperature is indicated in ° C or ° F.
The indicated range will be within ±20 ° C or ±20 ° F of the setting ranges shown
in the following table. (See note 1.)
Range in °C
Binary (4-digit Hex)
FF38 to FFFF to 0514
F200 to 1300
(−200 to −1 to 1,300)
(−200 to 1,300)
0000 to 1388
0000 to 5000
(0.0 to 500.0)
(0.0 to 500.0)
FF9C to FFFF to 0352
F100 to 0850
(−100 to −1 to 850)
(−100 to 850)
0000 to 0FA0
0000 to 4000
(0.0 to 400.0)
(0.0 to 400.0)
F830 to FFFF to 0FA0
F999 to 4000
(−200.0 to −0.1 to 400.0)
(−99.9 to 400.0)
See note 3.
FF9C to FFFF to 0352
F100 to 0850
(−100 to −1 to 850)
(−100 to 850)
0000 to 0FA0
0000 to 4000
(0.0 to 400.0)
(0.0 to 400.0)
0000 to 06A4
0000 to 1700
(0 to 1,700)
(0.0 to 1,700)
0000 to 06A4
0000 to 1700
(0 to 1,700)
(0.0 to 1,700)
0064 to 0708
0100 to 1800
(100 to 1,800)
(100 to 1,800)
Range in °C
Binary (4-digit Hex)
F830 to FFFF to 1964
F999 to 6500
(−200.0 to −0.1 to 650.0)
(−99.9 to 650.0)
See note 3.
F830 to FFFF to 1964
F999 to 6500
(−200.0 to −0.1 to 650.0)
(−99.9 to 650.0)
See note 3.
Settings 2 through 9 are not allowed.
1. If the allowed indication range is exceeded, a sensor error will occur, the
corresponding Sensor Error Flag will be turned ON, and the PV will contain
the data "CCCC." When a sensor error occurs, that control loop's control
output will be turned OFF. The alarm function will operate because the PV
indicates an abnormally high temperature.
4-digit BCD
Binary (4-digit Hex)
FED4 to FFFF to 08FC
(−300 to −1 to 2,300)
0000 to 2328
(0.0 to 900.0)
FF9C to FFFF to 05DC
(−100 to −1 to 1,500)
0000 to 1D4C
(0.0 to 750.0)
F448 to FFFF to 1B58
(−300.0 to −0.1 to 700.0)
FF9C to FFFF to 05DC
(−100 to −1 to 1,500)
0000 to 1D4C
(0.0 to 750.0)
0000 to 0BB8
(0 to 3,000)
0000 to 0BB8
(0 to 3,000)
012C to 0C80
(300 to 3,200)
4-digit BCD
Binary (4-digit Hex)
F448 to FFFF to 2EE0
(−300.0 to −0.1 to
1,200.0)
F448 to FFFF to 2EE0
(−300.0 to −0.1 to
1,200.0)
Settings 2 through 9 are not allowed.
Section 2-1
Range in °F
4-digit BCD
F300 to 2300
(−300 to 2,300)
0000 to 9000
(0.0 to 900.0)
F100 to 1500
(−100 to 1,500)
0000 to 7500
(0.0 to 750.0)
F999 to 7000
(−99.9 to 700.0)
See note 3.
F100 to 1500
(−100 to 1,500)
0000 to 7500
(0.0 to 750.0)
0000 to 3000
(0.0 to 3,000)
0000 to 3000
(0.0 to 3,000)
0300 to 3200
(300 to 3,200)
Range in °F
4-digit BCD
F999 to 9999
(−99.9 to 999.9)
See note 3.
F999 to 9999
(−99.9 to 999.9)
See note 3.