Data Ranges; Settings - Omron CJ Series Operation Manual

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Data Ranges

Starting DM Area Word
2-6

Data Ranges

2-6-1

Settings

Allocated word(s)
Loop 1: n
Loop 2: n+1
Loop 3: n+10
Loop 4: n+11
Two-loop Temperature
Control Units only:
Loop 1: n+10
Loop 2: n+11
Loops 1 and 2: D (m+0)
Loops 3 and 4: D (m+1)
Loop 1: D (m+2), D (m+3)
Loop 2: D (m+4), D (m+5)
Loop 3: D (m+6), D (m+7)
Loop 4: D (m+8), D (m+9)
Loop 1: D (m+10)
Loop 2: D (m+20)
Loop 3: D (m+50)
Loop 4: D (m+60)
Loop 1: D (m+11)
Loop 2: D (m+21)
Loop 3: D (m+51)
Loop 4: D (m+61)
Loop 1: D (m+12)
Loop 2: D (m+22)
Loop 3: D (m+52)
Loop 4: D (m+62)
The starting DM Area word (m) for a Special I/O Unit is:
m = 20000 + (100 × unit number)
• Starting CIO word: n = 2000 + (10 × unit number)
• Starting DM word: m = 20000 + (100 × unit number)
Setting
BCD range
SP (set point) Depends on the Input Type setting.
Refer to 2-1-3 Input Specifications
for details.
Heater Burn-
0000 to 0500
out Current
(See note 4.)
Alarm Mode
0000 to 9999
0: No alarm
1: Upper and lower-limit alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit range
alarm
5: Upper and lower-limit alarm with
standby sequence
6: Upper-limit alarm with standby
sequence
7: Lower-limit alarm with standby
sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
Alarm hyster-
0000 to 9999
esis
Alarm 1 SV
F999 to 9999
Alarm 2 SV
F999 to 9999
Input Com-
F999 to 9999
pensation
Value
Binary range
Units Default
°C or
0 or 0.0 RAM
°F
0000 to 01F4
A
0.0
0000 to 9999
---
0
°C or
0000 to 270F
0.0
°F
°C or
C3D8 to 3C28
0 or 0.0 The Temperature Con-
°F
°C or
C3D8 to 3C28
0 or 0.0
°F
°C or
FC19 to 270F
0 or 0.0
°F
Section 2-6
Memory protection
value
(Protect the contents
of memory in the CPU
Unit.)
RAM
(Protect the contents
of memory in the CPU
Unit.)
trol Unit's settings are
written to RAM. When
the Save Bit is turned
ON, the settings are
written to EEPROM.
(See notes 2 and 3.)
If DIP switch pin 8 is
ON, the settings are
automatically trans-
ferred from EEPROM
to the CPU Unit when
the power is turned
ON or the Tempera-
ture Control Unit is
restarted.
49