I/O Wiring Examples - Omron CJ Series Operation Manual

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Wiring
2-4-3

I/O Wiring Examples

Thermocouple
Temperature Control Units
CJ1W-TC001
(4 loops, NPN outputs)
CJ1W-TC001
Loop 2
Loop 1
Cold-
junction
Loop 4
Loop 3
CJ1W-TC002
(4 loops, PNP outputs)
CJ1W-TC002
Loop 2
Loop 1
Cold-
junction
Loop 4
Loop 3
• Do not touch or remove the cold-junction compensator.
• Use the type of sensor selected on the Input Type Switch.
• The Temperature Control Unit and Terminal Block are a matched set, so
use the Temperature Control Unit and Terminal Block with matching serial
numbers.
• Do not connect anything to the N.C. terminals. (The N.C. terminals cannot
even be used as junction terminals.)
• Do not connect any Current Transformer to the CT input terminals other
than an OMRON E54-CT1 or E54-CT3.
CJ1W-TC003
(2 loops, HB alarm, NPN
outputs)
CJ1W-TC003
Loop 2
Loop 1
Cold-
junction
Section 2-4
CJ1W-TC004
(2 loops, HB alarm, PNP
outputs)
CJ1W-TC004
Loop 2
Loop 1
Cold-
junction
27