Omron CJ Series Operation Manual page 37

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Specifications
Item
External terminal
Removable terminal block with 18 points (M3 screws)
connections
Effect on the CPU
0.4 ms
Unit's cycle time
Heater Burnout (HB)
Alarm
Current Transformer
(CT) Ratings
14
Note
1. The last three digits of the model number indicate the Unit's features:
CJ1W-TC @ 0 @
2.
Indication accuracy of thermocouples
• Accuracy ratings are given for the Temperature Control Unit used in a
set with a cold-junction compensator (on the terminal block). Always
use the Unit and terminal block in a set. There are labels with serial
numbers attached to the terminal blocks and Units to help keep track
of the sets.
• When returning a thermocouple-type Temperature Control Unit for re-
pair, always return the Unit and the terminal block (with the cold-junc-
tion compensator) as a set.
Item
Maximum heater current
Indication accuracy of input cur-
rent
Heater burnout alarm setting
range
Min. detectable ON time
(See note.)
Note If the control output is ON for less than 200 ms, the heater burnout detection
function will not operate and heater current measurement will not be per-
formed.
Item
Max. continuous heater current
Dielectric strength
Vibration resistance
Weight
Accessories
Specification
1: NPN outputs, four-loop control outputs
Output type
2: PNP outputs, four-loop control outputs
3: NPN outputs, two-loop control outputs and heater
burnout alarm outputs
4: PNP outputs, two-loop control outputs and heater
burnout alarm outputs
Always 0.
0: Thermocouple input
Input type
1: Platinum resistance thermometer input
Single-phase AC, 50 A
±5% of full scale ± 1 digit max.
0.1 to 49.9 A (0.1 A units)
The heater burnout detection function will not
operate if the set value is set to 0.0 A or 50.0 A.
(When the SV is 0.0 A, the heather burnout alarm
will be OFF. When the SV is 50.0 A, the heater
burnout alarm will be ON.)
200 ms
E54-CT1
50 A
1,000 VAC (1 min.)
50 Hz, 98 m/s
Approx. 11.5 g
None
Section 2-1
Specification
E54-CT3
120 A (See note 1.)
2
Approx. 50 g
Contacts (2)
Plugs (2)