Omron CJ Series Operation Manual page 36

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Specifications
Item
31 × 90 × 65 mm (W × H × D)
Dimensions
Weight
150 g max.
Characteristics
Item
Model number
CJ1W-TC00@
Temperature sensor
Thermocouple: Types R, S, K, J, T, L, and B
Number of loops
There are two types of Unit available: Four-loop Units and Two-loop Unit with heater burnout detec-
tion. (See note 1.)
Control output and
NPN or PNP outputs, both with short-circuit protection (See note 1.)
heater burnout alarm
Externally supplied power supply voltage: 24 VDC +10%/-15%
output
Maximum switching capacity: 100 mA (per output)
Leakage current: 0.3 mA max.
Residual voltage: 3 V max.
Temperature control
ON/OFF control or PID control with two degrees of freedom (Set with pin 6 on the Unit's DIP
method
switch.)
Control operation
Forward or reverse operation (Set with pins 4 and 5 on the Unit's DIP switch.)
RUN/STOP control
Supported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
Operation with CPU
The Temperature Control Unit can be set to continue operating or stop operating when the CPU
Unit in PROGRAM
Unit is in PROGRAM mode. (Set with pin 1 on the Unit's DIP switch.)
mode
Auto/Manual switch
None
for operational out-
put
Autotuning (AT) of
Supported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
PID constant
Indication accuracy
Centigrade: ±0.3% PV or ±1°C (whichever is
larger) ± 1 digit max.
Farenheit: ±0.3% PV or ±2°F (whichever is
larger) ± 1 digit max.
• The accuracy will be ±2°C ± 1 digit max. when
using an L-type thermocouple or using a K or
T-type thermocouple below −100°C.
• The accuracy will be ±3°C ± 1 digit max. when
using an R or S-type thermocouple below
200°C.
• The B-type thermocouples may not be accu-
rate below 400°C. (See note 2.)
0.0 to 999.9 °C or °F (0.1 °C or °F units)
Sensitivity (when
using ON/OFF con-
trol)
0.1 to 999.9 °C or °F (0.1 °C or °F units)
Proportional band
Integral (reset) time
0 to 9,999 s (one-second units)
Derivative (rate) time 0 to 9,999 s (one-second units)
Control period
1 to 99 s (one-second units)
Sampling period
500 ms (4 loops)
Output refresh
500 ms (4 loops)
period
Display refresh
500 ms (4 loops)
period
−99.9 to 999.9 °C or °F (0.1 °C or °F units)
Input compensation
value
−999 to 9,999 °C or °F (1 °C or °F units)
Alarm output setting
range
The setting range will be −99.9 to 999.9 °C or °F (0.1 °C or °F units) when using a platinum resis-
tance thermometer or using a K or J-type thermocouple in decimal-point mode.
Specification
Specification
CJ1W-TC10@
Platinum resistance thermometer: Types Pt100
and JPt100
Centigrade: ±0.3% PV or ±0.8°C (whichever is
larger) ± 1 digit max.
Farenheit: ±0.3% PV or ±1.6°F (whichever is
larger) ± 1 digit max.
Section 2-1
13