Section 1. Owner Information; Before You Call A Serviceman - Nordyne R-410A User Manual And Installation Instructions

15 seer 2-stage r-410a single package air conditioner
Table of Contents

Advertisement

SECTION 1.
OWNER INFORMATION
OPERATING INSTRUCTIONS
To Operate Your Air Conditioner for Cooling—
Thermostat — The 15 SEER Air Conditioner
uses a special two speed compressor to achieve
a high level of effi ciency in a compact frame. A
two stage cooling 24VAC thermostat can be
used with these units. For the highest effi ciency
the use of a two-stage cooling thermostat is
recommended. Refer to Figure 11 or 12 for a
unit wiring diagram.
Cooling Mode:
1.
On a call for cooling the thermostat closes,
applying 24VAC to the G and Y1 terminals
on the control. This closes the compressor
contactor, and the compressor operates on
1st stage.
2.
If the thermostat is not satisfi ed in the
required time, based on the operation of
the two-stage cooling thermostat, Y2 will
System
Fan
Mode
Mode
Figure 1. Typical Thermostat
energize and the compressor will run at
second stage. Refer to the thermostat
installation instructions for the cooling
profi le.
3.
When the thermostat is satisfi ed, the G
and Y terminals on the control board are
de-energized opening the compressor
contactor.
To Operate Your Unit for Heating — (If optional
heat accessory is installed.)
1. Set the thermostat system switch to HEAT or
AUTO and the thermostat fan switch to AUTO.
(See Figure 1)
2. Set the thermostat temperature to the desired
temperature level using the temperature selector.
Please refer to the separate user's manual for
complete thermostat programming instructions.
The indoor blower will cycle on and off to
maintain the indoor temperature at the desired
heating level.
To Shut Off Your Air Conditioner —Set the
thermostat system switch to OFF and the
thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the
thermostat temperature setting.
To Operate the Indoor Blower Continuously—
Set the thermostat fan switch to ON (See Figure 1)
The indoor blower will start immediately, and
will run continually until the fan switch is reset
to AUTO.
The continuous indoor blower operation can be
obtained with the thermostat system switch set
in any position, including OFF. The continuous
indoor blower operation is typically used to
circulate the indoor air to equalize a temperature
unbalance due to a sun load, cooking, or fi replace
operation.

BEFORE YOU CALL A SERVICEMAN

Let your serviceman check your system at the
start of each air conditioning season. He will
make sure it's working right, clean or change
fi lters and make any needed adjustments.
In addition, follow these simple rules:
1.
Never run your system without fi lter. If you
do, the cooling coils will get dirty and may
become clogged.
2.
Set your thermostat at the comfort level you
Temperature
wish -- and then leave it alone. Let it control
Selector
the operation of the air conditioning system.
If you get chilly, turn it up a degree at a time
until comfort is restored.
3.
It takes longer for an air conditioner to cool
your dwelling than it does for your furnace to
heat it. Therefore, do not turn the unit on and
expect a dramatic drop in temperature, at
least not right away. If your home is hot and
humid, the temperature will drop slowly.
4.
Check your fi lters every ten days in summer
to see if they are dirty. To keep them clean,
use a mild solution of detergent and water
on washable types. Replace non washable
fi lters.
5.
Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.
If your air conditioner isn't working:
1.
Make sure the fuses are not blown or that
your circuit breakers are on.
2.
See that your thermostat is set at the desired
temperature and that your system's switch
is on "Cool."
3