HP R1500 - UPS XR User Manual page 69

Hp 3 phase ups user guide
Table of Contents

Advertisement

Description
Relay Config
Signal Inputs
Serial Port Config
Parallel Operation Settings (only
available in parallel configuration)
Battery Setup
Power Strategy
Start Screen
User Password
Audible Alarms
Unsynchronized Transfer to
Bypass
Transfer to Bypass When
Overload
Automatic Start Delay
Control Commands from X-Slot 1
Control Commands from X-Slot
2/Serv
X-Slot Signal Input Activation
Available settings
Relay: [Alarm-1][X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [On Battery][Summary Alarm][On
Bypass][UPS OK][custom][empty]
[empty][Logic]
For more information, see "Programmable
signal inputs (on page 77)."
Port: [X-Slot-1][X-Slot 2/Serv]
Speed: [19200][9600][2400][1200]
Parallel Operation Mode: [Redundant
Mode][Capacity Mode]
This setting is not available for six-unit
systems (Redundant Mode only)
Parallel XCP: [System][Sub Unit]
Select System for HP communication
applications. Select Sub Unit for other
applications.
Auto ID Restart: [Done][Restart]
Select Restart to reinitialize
auto-identification. For more information,
see "Auto-identification (on page 78)."
Number of ERMs: [0 through 4]
For more information, see "Configuring the
UPS (on page 67)."
Battery Low Alarm Level:
[1.750 through 1.950 volts per cell]
Automatic Battery Tests:
[Enabled][Disabled]
Enabled automatically runs the battery test
once a month.
[High Efficiency][Standard]
For more information, see "Normal mode
(on page 65)."
HP logo
Mimic screen (on page 64)
[Enabled][Disabled]
If enabled is selected, the password is
USER.
[Normal Sound][Disabled]
[Allowed][Not Allowed]
[After a delay][Immediately]
-1 through 32767 seconds
(-1 means disabled)
[Allowed][Not Allowed]
[Allowed][Not Allowed]
0 through 65 seconds
Default setting
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS OK
#2: On Bypass
#3: Summary Alarm
#4: On Battery
<empty>
19200
Redundant Mode
System
None
0
(internal batteries only)
1.880 V/cell
Enabled
High Efficiency
HP logo
Disabled
Normal Sound
Not Allowed
After a delay
0s
Allowed
Allowed
5s
UPS operations 69