Installing The Isr 9024 Power Supply Unit; Operating The Isr 9024 Interconnect; Troubleshooting The Isr 9024 - HP Cluster Platform Interconnects v2010 User Manual

Hp cluster platform infiniband interconnect installation and user's guide
Hide thumbs Also See for Cluster Platform Interconnects v2010:
Table of Contents

Advertisement

2.4 Installing the ISR 9024 Power Supply Unit

An ISR 9024 contains either one or two power supplies in the side bays of the unit chassis, as
shown in
Figure
Warning:
To maintain the correct cooling air flow, you must fill an unused power supply bay by using the
supplied blank filler panel
Use the following procedure to install or remove a power supply. You can do this when the
interconnect is running
1.
Unscrew the captive fasteners at each side of the filler panel and remove it from the front
panel. Retain the filler panel for future use.
2.
Position the rear (connector end) of the power supply in the empty bay.
3.
Holding the power supply level with the chassis, slide it into the slot until it meets resistance
at the chassis connector. Do not force the unit if you feel resistance, ensure that it is level
and square with the bay.
4.
Push the module further until it is completely seated on the connector, and its bezel is flush
with the chassis front panel.
5.
Use the captive fasteners at each side of the power supply to secure it in place.

2.5 Operating the ISR 9024 Interconnect

To power up the interconnect and begin using it, use the following procedure:
1.
Ensure that the following tasks are complete:
a.
The chassis is secured in the rack.
b.
Cabling is complete as described in
c.
If not already connected, connect a power supply cable to the IEC inlets for each PSU
installed (maximum two cables) to the adjacent power strip outlets located in the sides
of the rack.
d.
All other cluster components are installed, cabled, and powered up.
2.
Apply power to the interconnect, and verify the following LED status:
a.
The green power supply indicators at the front panel are illuminated.
b.
The green status LED on the front panel that is labelled SYS is illuminated.
c.
The green status LED on the front panel that is labelled SM is illuminated as follows:
d.
The green status LED on the front panel that is labelled PS is illuminated.
3.
For each port that has a connected InfiniBand link cable:
a.
The green physical link LED is illuminated.
b.
The amber logical link LED is illuminated in one of the following states:

2.6 Troubleshooting the ISR 9024

If any indicators are not illuminated as described in the preceding list, use the following
verification procedure:
1.
The PS LED does not illuminate.
2.
The PSU is faulty. Replace the PSU.
36
Installing and Maintaining the ISR 9024 Interconnect
2-3.
Constant, for active mode.
Flashing, for standby mode.
Constant, indicating the presence of a link with no data traffic passing over the
link
Flashing, indicating the presence of a link with data traffic passing over the link.
Chapter
7.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cluster platform

Table of Contents