Generator Outputs - MULTIQUIP WhisperWatt DCA45SSKU3 Operation And Parts Manual

60hz generator (kubota v3800-di-t diesel engine)
Table of Contents

Advertisement

generaTor ouTpuT volTages
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
voltage selector switch
The voltage selector switch (Figure 13) is located above
the output terminal panel's Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
voltage selector switch locking Button
To lock the voltage selector switch, press and hold the
red button located at the bottom of the switch. While
holding the red button down, insert a pad lock into the hole
next to the button to retain it in the inward locked position.
When the lock is removed, the red button is spring loaded
and will return to its normal outward unlocked position.
CauTion
never change the position of the voltage selector
switch while the engine is running. alWaYs place
circuit breaker in the oFF position before selecting
voltage.
Table 7. voltages available
uvWo output
voltage selector switch
Terminal lugs
3-phase 240/139v position
3Ø line-line
208V
1Ø line-neutral
120V
voltage selector switch single-phase 240/120v position
1Ø line-neutral/
120V
Line-Neutral
line-line
page 24 — DCa45ssk/ku3 60 hz generaTor • operaTion anD parTs manual — rev. #0 (12/15/11)
voltage selector switch
3-phase 480/270v position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line

generatOr Outputs

generator amperage
Table 8 shows the maximum amps the generator can
provide. Do noT exceed the maximum amps as listed..
Table 8. generator maximum amps
rated voltage
1Ø 120 Volt
1Ø 240 Volt
3Ø 240 Volt
3Ø 480 Volt
gFCi receptacle load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
Table 9. 1Ø gFCi receptacle load Capacity
Twist lock (C6369)
Table 10. 3Ø generator maximum amps
(uvWo Terminals)
480V
277V
N/A
maximum amps
100 amps (4 wire)
108A x 2 (Zigzag)
50 amps (4 wire)
108A (Zigzag)
108 amps
54 amps
kW in use
available load
Current (amps)
GFCI Duplex
1Ø 240/120V
5-20R 120V
26
0
24.8
5 amps/receptacle
23.6
10 amps/receptacle
22.4
15 amps/receptacle
21.2
20 amps/receptacle
kva in use
available load
Current (amps)
GFCI Duplex
3Ø 240/480V
5-20R 120V
45
0 amps/receptacle
40.9
5 amps/receptacle
36.7
10 amps/receptacle
32.6
15 amps/receptacle
28.4
20 amps/receptacle