Generator Outputs - MULTIQUIP Whisperwatt DCA150SSJU4F Operation And Parts Manual

60hz
Table of Contents

Advertisement

generator output voltages
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 12). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
voltage selector switch
The voltage selector switch (Figure 12) is located above
the output terminal panel's Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection..
Figure 12. Voltage Selector Switch
caution
never change the position of the voltage selector
switch while the engine is running. alWaYs place
circuit breaker in the OFF position before selecting
voltage.
table 7. voltages available
uvWo output
voltage selector switch
terminal lugs
3-phase 240/139v position
3Ø line-line
208V
1Ø line-neutral
120V
voltage selector switch single-phase 240/120v position
1Ø line-neutral/
120V
Line-Neutral
line-line
page 24 — dca150ssju4f 60 hz generator • operation and parts manual — rev. #0 (11/06/14)
voltage selector switch
3-phase 480/270v position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line

GeNeratOr OUtpUts

maximum amps
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
table 8. generator maximum amps
rated voltage
1Ø 120 Volt
1Ø 240 Volt
3Ø 240 Volt
3Ø 480 Volt
480V
277V
N/A
maximum amps
333.3 X 2 amps (4 wire)
361 amps X 2 (Zigzag)
166.7 amps (4 wire)
361 amps (Zigzag)
400 amps
180 amps