Generator Outputs - MULTIQUIP WhisperWatt DCA300SSC Operation And Parts Manual

Whisperwatt series 60hz generator
Table of Contents

Advertisement

generator oUtpUt voltageS
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage change-over board
(Figure 12). To obtain some of the voltages as listed in
Table 7 (see below) will require a fine adjustment using
the voltage regulator (VR) control knob located on the
control panel.
voltage Change-over Board
The voltage change-over board (Figure 12) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Figure 12. Voltage Change-Over Board
CaUtion
never attempt to place jumper plates on the voltage
change-over board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
table 7. voltages available
UvWo output
voltage Change-over Board
terminal lugs
3-phase 240/139v position
208V
3Ø line-line
1Ø line-neutral
120V
voltage Change-over Board Single-phase 240/120v position
1Ø line-neutral/
120V
Line-Neutral
line-line
page 26 — DCa300SSC / DCa300SSCU gen. • operation anD partS manUal — rev. #1 (08/10/11)
voltage Change-over Board
3-phase 480/270v position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line

generatOr OUtpUts

maximum amps
Table 8 shows the maximum amps the generator can
provide. Do not exceed the maximum amps as listed.
table 8. generator maximum amps
model
rated voltage
Single Phase 120 Volt
Single Phase 240 Volt
Three Phase 240 Volt
Three Phase 480 Volt
480V
277V
N/A
DCA300SSC
DCA300SSCU
maximum amps
666.7 amps (4 wire)
333.3 amps (4 wire)
722 amps
361 amps

Advertisement

Table of Contents
loading

This manual is also suitable for:

Whisperwatt dca300sscu

Table of Contents