EDUS041111_a
CAUTION
•
When connecting the connection wires to the terminal board
using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fi
Strip wire end
to this point.
3)
Pull the wire and make sure that it does not disconnect. Then fi
Facility Setting
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)).
Never use it in a residence or offi
Cutting jumper 6 (J6) on the circuit board will expand the operation range down to 5˚F (–15˚C). However it will stop if the
outdoor temperature drops below –4˚F (–20˚C) and start back up once the temperature rises again.
1)
Remove the 3 screws on the side and remove the top plate of the outdoor unit.
2)
Remove the drip proof cover.
3)
Cut the jumper (J6) of the PCB inside.
1) Remove the
CAUTION
•
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
•
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
•
Do not place humidifi
A humidifi
er might cause dew jumping from the indoor unit outlet vent.
•
Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
Room Air Conditioners K-Series
Excessive strip length
may cause electrical
shock or leakage.
Good
Wrong
ce (the space where there is a human).
3 screws.
Drip proof cover
ers or other items which might raise the humidity in rooms where facility settings are being used.
res.
x the wire in place with a wire stop.
Installation Manual
Stripping wire at terminal block
Top plate
2) Remove the drip
proof cover.
PCB
3) Cut jumper J6.
89