Overload Operation - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 80 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

6.16 Overload Operation

When the UPS is operating and an overload condition is detected the following screen is
displayed.
After a period of time, if the overload is still not reduced and the RUN/STOP key switch is in the
RUN position, the UPS will transfer to bypass automatically. If the overload condition is still
present, the following screen will be displayed:
If the RUN/STOP key switch is in the STOP position, the UPS is in the bypass mode, and if the
overload condition is still present, the following screen will be displayed:
After the load is reduced and if the RUN/STOP key switch is in the RUN position, the UPS will
return to the Inverter mode of operation after a period of time. During the wait time the following
screen will be displayed:
Or if the UPS is waiting and the RUN/STOP key switch is switched to the STOP position while
the UPS is waiting the following screen will be displayed:
If the RUN/STOP key switch remains in the STOP position when the wait period of the UPS is
complete the following screen will be displayed:
4200 FA User's Manual
TOSHIBA
- UPS ON-LINE -
OUTPUT VOLTAGE= ###V
OUTPUT CURRENT= ###%
* UPS OL: REDUCE LOAD *
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
DATE (DAY) TIME
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
DATE (DAY) TIME
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
CURRENT= 100/100/100
>PLEASE WAIT
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
CURRENT= 100/100/100
>PLEASE WAIT
- BYPASS OPERATION -
OUTPUT VOLATAGE=###V
CURRENT=100\100\100%
DATE (DAY) TIME
Note: ### indicates an actual
numerical value.
49

Advertisement

Table of Contents
loading

Table of Contents