Rs-232C - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

4.5.2

RS-232C

The RS-232C serial communication interface is available through a DB9 female connector located
on the inside of the UPS.
RemotEye II Mounting Location – 15-30kVA
This interface allows control of the UPS from a computer network running TOSHIBA RemotEyeII
software. The computer and the UPS are connected through a serial RS-232C communication port.
The available data from the UPS, via the RS-232C communication link, is shown below:
Operating Conditions
UPS Operating Status
(Described as "yes or "no")
Fault Details
(Described as "occurred" or "not occurred")
4200FA Installation and Operation Manual
RemotEye II
Module
RemotEye II Mounting Location – 50kVA
Input Voltage
Input Frequency
Battery Voltage
Utility Power OK
Low Battery Voltage Detected
UPS in BYPASS Mode
UPS in NORMAL Mode
Input and Output Frequency Synchronized
UPS FAULT Occurred
DC Bus Over-Current
DC Bus Over-Voltage
DC Bus Under-Voltage
Input Over-Current
Overheat
Overload Being Timed
Overload (allowable time exceeded)
Output Over-Voltage (during Normal Mode)
Output Under-Voltage (during Normal Mode)
Output Voltage
Output Frequency
Output Current