589A024-036 With Optional Base Rail, Unit Dimension - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit
. . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side
. . . . . . . . . . . . . . . . 42 (1067)
UNIT
ELECTRICAL
589A
CHARACTERISTICS
024040
208/230-1-60
024060
208/230-1-60
030040
208/230-1-60
030060/080
208/230-1-60
036060/080
208/230-1-60, 208/230-3-60, 460-3-60
036100/120
208/230-1-60, 208/230-3-60, 460-3-60
CENTER OF GRAVITY (in./mm)
UNIT
589A
X
024040
26.57/674.9
024060
26.51/673.3
030040
26.90/683.3
030060/080
26.83/681.5
036060/080
26.99/685.5
036100/120
26.92/683.8
UNIT WEIGHT
lb
357
369
360
372
390
402
Y
Z
20.17/512.3
14.96/380.0
20.22/513.6
14.96/380.0
21.09/535.7
14.96/380.0
21.11/536.2
14.96/380.0
21.14/537.0
14.96/380.0
21.14/537.0
14.96/380.0
Fig. 7 — 589A024-036 With Optional Base Rail, Unit Dimensions
CORNER WEIGHT
(lb/kg)
kg
A
B
163
110/50
56/25
168
113/51
59/27
164
103/47
72/33
169
106/48
75/34
177
100/45
90/41
183
103/47
93/42
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
—7—
C
D
136/62
55/25
139/63
58/26
124/56
61/28
127/58
64/29
123/56
77/35
127/57
80/36
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required