588A018-042 Without Base Rail, Unit Dimensions; Rear View; Left Side View; Front View - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
588A
CHARACTERISTICS
018040
024040
024060
030040
208/230-1-60, 208/230-3-60
030060/080
208/230-1-60, 208/230-3-60
036060/080
208/230-1-60, 208/230-3-60, 460-3-60
036100/120
208/230-1-60, 208/230-3-60, 460-3-60
042060/080
208/230-1-60, 208/230-3-60, 460-3-60
042100/120
208/230-1-60, 208/230-3-60, 460-3-60
UNIT
F
588A
in./mm
018040
024040
024060
030040
16
9
/420.7
18
16
030060/080
036060/080
036100/120
042060/080
20
/522.3
22
9
16
042100/120
ELECTRICAL
208/230-1-60
208/230-1-60
208/230-1-60
CENTER OF GRAVITY in./mm
G
in./mm
X
Y
25.07/637
20.59/523
27.07/688
23.35/593
26.98/685
23.27/591
15
/481.0
26.71/678
23.46/596
16
27.15/689
22.36/568
27.50/698
22.48/571
27.40/696
22.44/570
27.01/686
22.44/570
/582.6
15
16
26.94/684
22.44/570
Fig. 2 — 588A018-042 Without Base Rail, Unit Dimensions
UNIT WEIGHT
lb
kg
A
272
123
81/37
303
138
97/44
315
143
100/45
320
145
100/45
332
149
103/46
336
153
86/39
348
158
89/40
375
170
95/43
387
176
98/45
CG
— Center of Gravity
Z
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
10.85/276
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
12.7/321
—2—
CORNER WEIGHT
(lb/kg)
B
C
D
62/28
76/35
53/24
43/20
123/56
40/18
46/21
126/57
43/20
47/21
126/57
47/21
50/22
129/58
50/23
76/35
111/50
63/29
79/36
114/52
66/30
86/39
119/54
75/34
89/40
122/55
78/35
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required
UNIT HEIGHT
(in./mm)
E
24.1/613
24.1/613
24.1/613
24.1/613
24.1/613
24.1/613
24.1/613
28.1/714
28.1/714

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

589a

Table of Contents