588A048,060 Without Base Rail, Unit Dimensions - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

UNIT
588A
CHARACTERISTICS
048080
208/230-1-60, 208/230-3-60, 460-3-60
048100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
060080
208/230-1-60, 208/230-3-60, 460-3-60
060100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
CENTER OF GRAVITY (in./mm)
UNIT
588A
X
048080
28.76/731
048100/120/140
28.42/722
060080
28.36/720
060100/120/140
27.95/710
ELECTRICAL
Y
Z
23.46/596
15.35/390
23.42/595
15.35/390
23.27/591
15.35/390
23.23/590
15.35/390
Fig. 4 — 588A048,060 Without Base Rail, Unit Dimensions
REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT WEIGHT
lb
kg
A
414
188
107/49
426
193
110/50
453
206
117/53
465
211
120/55
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
—4—
CORNER WEIGHT
(lb/kg)
B
C
D
83/38
158/72
66/30
86/39
159/72
71/32
93/42
167/76
76/35
96/44
167/76
82/37
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required