Base Unit Dimensions — 580D036-072 - Bryant 580D Product Information Manual

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons
Table of Contents

Advertisement

NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only.
For horizontal discharge units, field-supplied flanges should be attached to horizon-
tal discharge openings, and all ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch. Bottom of
base rail to combustible surfaces (when not using curb) 0 inches.
BASE UNIT DIMENSIONS — 580D036-072
*
Weights are for unit only (aluminum plate fins) and do not include options or crating.
A
B
C
17
CORNER WEIGHT*
UNIT
A
B
580D
lb
kg
lb
036
140
63.5
105
048
142
64.4
106
060
150
68.0
115
072
165
74.8
136
CONNECTION SIZES
1
1
Dia. [27] Field Power
16
Supply Hole
3
— 14 NPT Condensate
4
Drain
—14 NPT Gas Connection
1
2
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side get-
ting the greater clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control
box side, 42 in. per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as
stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C
roof covering material if set on baserail.
8. The vertical center of gravity is 1 -6 [457] up from the bottom of the base rail. Hori-
zontal center of gravity is shown.
C
D
kg
lb
kg
lb
47.6
159
72.1
56
25.4
48.1
162
73.5
60
27.2
52.2
160
72.6
65
29.5
61.7
200
90.7
64
29.0
BOTTOM POWER CHART, THESE
HOLES REQUIRED FOR USE WITH
ACCESSORY PACKAGES —
CRBTMPWR001A00 (
1
,
3
)
2
4
CRBTMPWR002A00 (
, 1
1
1
2
4
THREADED
REQUIRED
CONDUIT
WIRE SIZE
HOLE SIZES
SIZE
(MAX)
1
24 V
7
[22.2]
2
8
Power†
1
[28.4]
3
1
4
8
1
1
Power†
1
3
[44.4]
4
4
†Select either
or 1
for power, depending
3
1
4
4
on wire size.
kg
)